Mitsubishi P288T(Y)SJMU-A PUHY-P312 User Manual

Page of 334
VIII  Test Run Mode ]
- 144 -
HWE09120
GB
Operation
Outdoor unit model
PUHY-P240TSJMU-A
PUHY-P120TJMU-A
PUHY-P120TJMU-A
Operating 
conditions
Ambient 
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor 
unit
No. of connected 
units
Unit
6
No. of units in opera-
tion
6
Model
-
18/36/36/36/48/48
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
25 [55]
Outdoor 
unit
Electric current
A
59.7
Voltage
V
230
Compressor frequency
Hz
81
81
LEV open-
ing
Indoor unit
Pulse
373/332/332/332/406/406
SC (LEV1) 
0
LEV2
2100
2100
Pressure
High pressure (after O/S)/low 
pressure (before accumulator)
MPa
[psi]
2.70/0.65 [392/94]
2.70/0.65 [392/94]
Temp. of 
each sec-
tion
Outdoor 
unit
Discharge (TH4)
°C [°F]
70 [158]
70 [158]
Heat exchanger out-
let (TH3)
-1 [30]
-1 [30]
Accumulator inlet
-1 [30]
-1 [30]
Accumulator outlet
-1 [30]
-1 [30]
Compressor inlet
-1 [30]
-1 [30]
Compressor shell 
bottom
40 [104]
40 [104]
Indoor 
unit
LEV inlet
36 [97]
36 [97]
Heat exchanger  
inlet
69 [156]
69 [156]