Mitsubishi P120 User Manual

Page of 334
VII  Control ]
- 116 -
HWE09120
GB
(2)  Outdoor unit (cooling and heating modes)
*Note 1. 
For about 3 minutes after power on, search for the indoor unit address, for the remote controller address,  
            and for the group information will start. During this, "HO" / "PLEASE WAIT" blinks on the display of the remote  
            controller. When the indoor unit to be controlled by the remote controller is missing, "HO" / "PLEASE WAIT" keeps  
            blinking on the display of the remote controller even after 3 or more minutes after power on. 
*Note 2. 
The system may go into the error mode on either the indoor unit or the outdoor unit side. The outdoor stops only  
             when all of the connected indoor units are experiencing problems. The operation of even a single indoor unit will  
             keep the outdoor unit running. The error will be indicated on the LED display. 
*Note 3. 
The outdoor unit operates according to the operation mode commanded by the indoor unit. However, when the  
             outdoor unit is running a cooling operation, come of the operating indoor units will stop, or the operation of these  
             indoor units will be prohibited even when the indoor unit mode is switched from fan mode to heating mode.  
             This also applies when the outdoor unit is running a heating operation. 
Start 
Breaker  
turned on 
Operation  
command 
Error stop 
Error display on the  
outdoor unit LED 
Error command to  
indoor unit 
Operation  
mode 
Operation  
mode 
Error mode 
72C ON 
*Note 1 
*Note 3 
*Note 2 
YES 
YES 
YES 
YES 
NO 
NO 
NO 
NO 
"HO" / "PLEASE WAIT" blinks on  
the remote controller 
Operation command to indoor unit To  1 .
Cooling / Heating
1. Protection function self-holding cancelled. 
2. LEV1 fully closed. 
Normal operation 
1. 72C OFF 
2. Inverter output  0Hz 
3. Fan stop 
4. All solenoid valves OFF 
Refer to Cooling/Dry  
Operation 2-(1) and 2-(3) 
Refer to heating  
Operation 2-(2). 
From indoor unit 
Error 
Unit in the stopped state 
Self-holding of  
protection function 
Indoor units  
registered to the  
remote controller