Mitsubishi P120 User Manual
[
IX Troubleshooting ]
- 263 -
HWE09120
GB
(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the
INV board er-
ror detection
circuit.
Check the
INV board er-
ror detection
circuit.
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Overcurrent error
Error code: 4250
Detail code: No. 101, 104, 105,
106, and 107
Error code: 4250
Detail code: No. 101, 104, 105,
106, and 107
Replace the INV board.
(2)
Put the outdoor unit
into operation.
into operation.
2)
Logic error
Error code: 4220
Detail code: No. 111
Error code: 4220
Detail code: No. 111
Replace the INV board.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Error code: 5301
Detail code: No.117
Replace the INV board.
4)
IPM open
Error code: 5301
Detail code: No.119
Error code: 5301
Detail code: No.119
Normal
[2]
Check for
compressor
ground fault
or coil error.
Check for
compressor
ground fault
or coil error.
Disconnect the compressor
wiring, and check the com-
pressor Meg, and coil resis-
tance.
wiring, and check the com-
pressor Meg, and coil resis-
tance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
Error if less than 1 Mohm.
Check that there is no liquid re-
frigerant in the compressor.
If there is none, replace the com-
pressor.
frigerant in the compressor.
If there is none, replace the com-
pressor.
2)
Compressor coil resistance failure
Coil resistance value of 0.71 ohm
(20°C [68°F]): P72 model
Coil resistance value of 0.32 ohm
(20°C [68°F]): P96 - P144 models
Coil resistance value of 0.71 ohm
(20°C [68°F]): P72 model
Coil resistance value of 0.32 ohm
(20°C [68°F]): P96 - P144 models
Replace the compressor.
[3]
Check wheth-
er the inverter
is damaged.
(No load)
Check wheth-
er the inverter
is damaged.
(No load)
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Inverter-related problems are de-
tected.
tected.
Connect the short-circuit connec-
tor to CN6, and go to section [1].
tor to CN6, and go to section [1].
(2)
Disconnect the short-
circuit connector from
CN6 on the INV
board.
circuit connector from
CN6 on the INV
board.
2)
Inverter voltage is not output at the
terminals (SC-U, SC-V, and SC-W)
terminals (SC-U, SC-V, and SC-W)
Replace the INV board.
(3)
Put the outdoor unit
into operation.
Check the inverter
output voltage after
the inverter output
frequency has stabi-
lized.
into operation.
Check the inverter
output voltage after
the inverter output
frequency has stabi-
lized.
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
tween the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
4)
There is no voltage imbalance be-
tween the wires.
tween the wires.
Normal
*Reconnect the short-circuit con-
nector to CN6 after checking the
voltage.
*Reconnect the short-circuit con-
nector to CN6 after checking the
voltage.
[YJMU-A]