Mitsubishi P120 User Manual

Page of 334
IX  Troubleshooting ]
- 272 -
HWE09120
GB
-7- Control Circuit (YJMU-A)
(1) Control power source function block
1)   PUHY-P72, P96, P120, P144YJMU-A
Outdoor unit 
Power source system (AC 230 / 460 V)
Control system (DC 5 ~ 30 V) 
 * MA remote controllers and ME remote controllers cannot be used together.
(Both the ME and MA remote controller can be connected to a system with a system controller.)
A, B 
A, B 
M-NET  
transmission line 
(Non-polar 2 wire) 
AC 220 / 240 V
AC Power source 
To next unit 
(Indoor unit) 
MA
 remote controller wiring 
(Non-polar 2 wire) 
DC 17 ~ 30 V 
DC 9 ~ 12 V 
TB2 
 
TB15 
 
Terminal block for 
 power source 
TB5 
Terminal block  
for MA remote  
controller 
Terminal block  
for transmission  
line connection 
DC 17 ~ 30 V 
AC 460V
Terminal block for  
power source 
TB1 
 
Noise filter
Noise filter 
Fuse
Fuse
Fuse
72C, LEV
Fuse
Surge protection
INV board 
Control board
Fan board 
63H1
72C 
DCL 
DC / DC converter
Detection circuit for 
the power supply to 
the transmission line
M-NET board
DC / DC 
converter
Microcomputer
Microcomputer 
Microcomputer
5 V Power supply
18 V Power supply
12V Power supply
30 V Power supply
Relay drive circuit
Relay
5 V Power supply
5 V Power supply 
17V Power supply 
Smoothing capacitor 
Inverter 
Inverter 
Inverter drive 
circuit
Inverter drive  
circuit 
Inverter reset
circuit
Rectifier 
Compressor 
Heat  
exchanger  
fan 
Relay, LEV
Drive circuit
Solenoid valve
4-way valve
CH11
CN40
Terminal block for  
transmission line  
for centralized control 
(DC 24 ~ 30 V) 
TB7 
Indoor/outdoor  
transmission block 
(DC 24 ~ 30 V) 
TB3 
 
Rectifier
Trans Box
ME remote 
controller
MA remote  
controller 
Indoor unit 
Oudoor unit
                                    [YJMU-A]