Self-Diagnosis Function Table
1
2
3
4
5
6
7
8
1. Self-Diagnosis Function Table
1. Self-Diagnosis Function Table
• 
Causes and corrections in instances when automatic address setting cannot be started
• 
Causes and corrections in instances when automatic address setting starts, but cannot be completed successfully
• 
If alarm E15, E16, or E20 appears after automatic address setting is started, check the following items.
Trouble
Cause and correction
Trouble
Cause and correction
The power LED (D53) on the outdoor unit control PCB does not turn ON.
LED 1 and 2 on the outdoor unit control PCB do not turn OFF when 
the outdoor unit power is turned ON, and automatic address setting 
cannot be started.
An alarm appears immediately when automatic address setting is 
started from the wired remote controller.
Nothing happens when the operator attempts to start automatic 
address setting from the wired remote controller.
Check for any errors in the power wiring to 
the outdoor unit, and check for a missing 
phase.
Check the “Alarm Display” table and 
correct the problem.
(Refer to Section 3 Trouble Diagnosis)
Check that the wired remote controller 
wiring and the inter-unit control wiring are 
connected correctly.
Check that the indoor unit power is ON.
An alarm appears on the wired remote controller sometime from several 
seconds to several minutes after automatic address setting is started.
LED 1 and 2 on the outdoor unit control PCB indicate that automatic 
address setting is in progress (the LEDs blink alternately) for several 
minutes after automatic address setting is started (the compressors 
may also start and stop several times), however LED 1 and 2 never 
indicate that automatic address setting is completed (turn OFF).
Check the “Alarm Display” table and 
correct the problem. 
(Refer to Section 3 Trouble Diagnosis.)
Check the alarm details on the “Outdoor 
Unit Control PCB LED 1 and 2 Alarms” , 
then correct the problem.
Alarm display
E15
E16
E20
Alarm description
The number of indoor units detected during automatic address setting was smaller than the 
number of indoor units which was set with switch S004 and S005 on the outdoor unit PCB.
The number of indoor units detected during automatic address setting was larger than the 
number of indoor units which was set with switch S004 and S005 on the outdoor unit PCB.
The outdoor unit received no serial signals from indoor units within 90 seconds after automatic 
address setting was started.