1-10
Test Run
1
2
3
4
5
6
7
8
3. Auto Address Setting
Case 3B   Automatic Address Setting in Cooling Mode
Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor 
unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all 
refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.
Automatic Address Setting from Outdoor Unit
1.  Perform steps 1 - 4 in the same way as for   Case 2  .
5.  Turn the indoor and outdoor unit power ON at all systems.
6.   To perform automatic address setting in  Cooling mode  , on the outdoor main unit control PCB in the refrigerant system 
where you wish to set the addresses, short-circuit the mode change 2P pin (CN101). At the same time, short-circuit the 
automatic address pin (CN100) for 1 second or longer, then release it. (Be sure to perform this process for one system at a 
time. Automatic address settings cannot be performed for more than one system at the same time.)
 
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling 
mode begins.)
(All indoor units operate.)
*  To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it. The 
LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to 
perform automatic address setting again.
 
(Automatic address setting is completed when the compressors stop and LED 1 and 2 on the outdoor main unit control PCB 
turn OFF.)
7.  At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or 
longer, then release it.
 
(Repeat the same steps to complete automatic address setting for all units.)
8.  Operation from the remote controllers is now possible.
*  Automatic address setting in Cooling mode cannot be done from the remote controller.
Automatic Address Setting* from the Remote Controller
Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code “A1.”
1.  Press the remote controller timer time 
 button and 
 button at the same 
time. 
(Press and hold for 4 seconds or longer.)
2.  Next, press either the temperature setting 
 or 
 button. (Check that 
the item code is “A1.”)
3.  Use either the 
 or 
 button to set the system No. to perform auto-
matic address setting.
4.  Then press the 
 button.
 
(Automatic address setting for one refrigerant system begins.)
 
(When automatic address setting for one system is completed, the system returns 
to normal stopped status.) <Approximately 4 - 5 minutes is required.>
 
(During automatic address setting, “NOW SETTING” is displayed on the remote 
controller. This message disappears when automatic address setting is completed.)
5.  Repeat the same steps to perform automatic address setting for each successive system.