Sanyo UHX1252 User Manual

Page of 114
2-42
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Remote Control Functions
2
1
4
5
3
NOTE:
The temperature on the remote controller is displayed 
in Celusis (C).
Please note that you will not mistakenly read it 
in Fahrenheit (F) on the display.
Sensor Temperature Diaplay
3. Timer Remote Controller (RCS-TM80BG)
02
Intake temp.
03
E1
04
05
E3
06
Discharge temp.
07
Discharge temp. setting
08
Position of indoor unit
Motor Operated Valve (MOV)
0A
2A
4A
6A
0B
2B
4B
6B
0C
2C
4C
6C
0D
2D
4D
6D
0E
2E
4E
6E
0F
2F
4F
6F
10
30
50
70
11
31
51
71
12
32
52
72
13
33
53
73
14
34
54
74
15
35
55
75
16
36
56
76
17
37
57
77
18
38
58
78
19
39
59
79
1A
3A
5A
7A
1B
3B
5B
7B
1C
3C
5C
7C
1D
3D
5D
7D
1E
3E
5E
7E
1F
3F
5F
7F
20
40
60
80
21
41
61
81
22
42
62
82
Discharge temp. 3
Outdoor air temp.
CT2
CT3
Low-pressure sensor temp.
Suction temp.
Oil 1
Oil 2
Oil 3
Heat exchanger liquid 1
Heat exchanger gas 1
Heat exchanger liquid 2
Heat exchanger gas 2
High-pressure sensor temp.
Discharge temp. 2
Discharge temp. 1
  Sensor Temperature Display Function 
(displayed regardless of whether unit is 
operating or stopped)
The procedure below displays the sensor tempera-
tures from the remote controller, indoor unit, and out-
door unit on the remote controller.
<Procedure>
 Press and hold the 
 and 
 buttons 
simultaneously for 4 seconds or longer.
 The unit No. “X-X” (main unit No.), item code “XX” 
(sensor address), and servicing monitor “
XX” 
(sensor temperature) are displayed on the remote 
controller LCD display. 
 Press the temperature setting 
 / 
 
buttons and select the item code to the address of 
the sensor to monitor.
(For the relationships between the sensor 
addresses and sensor types, refer to the table of 
temperature sensors and addresses below.)
 If group control is in effect, press the 
 
button to select the unit to monitor.
Press the temperature setting  buttons 
to select the item code to change.
 Press  the 
 button to return to 
normal remote controller display.
NOTE
The temperature display appears as “- - - -” 
for units that are not connected.
*  
If monitor mode is engaged while normal 
operation is in progress, only the parts of 
the LCD display shown in the figure will 
change. Other parts continue to display 
the same information as during normal 
operation.
SM830157_W-2WAY_ECO-i.indb   42
SM830157_W-2WAY_ECO-i.indb   42
2007/06/08   14:23:41
2007/06/08   14:23:41