12-3-10.  Outdoor Unit Compressor Motor Defective
Check if compressor motor is locked up.
Set temperature by remote controller so air conditioner operates under Thermo. ON in cooling operation, then
start operation.
Check if compressor operates.
Measure resistance of compressor motor.
Disconnect each wire from the top of the compressor and measure resistance of each phase.
No abnormalities, proceed to check 
.
In case of abnormality 
Stops in 2 to 5 seconds. Humming of compressor motor can be heard.
After auto restart by 3-minute timer, same thing happens. If this condition contin-
ues, replace the compressor motor.
Caution: Carry out this check only after cutting power at the mains or disconnecting unit from the power 
supply.
In case of abnormality 
Replace compressor.
Phase
Resistance
Normal
R – S
1 – 5 
Ω
S – C
1 – 5 
Ω
C – R
1 – 5 
Ω
*
Use a circuit tester (set to 
Ω
range).
12-4. Outdoor Unit Fan Does Not Work
12-4-1.  Outdoor Unit Fan Motor Defective
Check if outdoor unit fan is locked up.
Turn fan gently by hand.
When fan does not turn easily 
Replace fan motor.
No abnormalities, proceed to check 
.
*
Use a circuit tester (set to 
Ω
range).
Measure resistance between each wire.
In case of abnormality 
Replace fan motor.
No abnormalities, check continuity of each wire (PNK, BRN and BLU).
Color
Resistance
Normal
BLU – BRN
70 – 150 
Ω
BLU – PNK
300 – 500 
Ω