Lg Electronics LCN240CP User Manual

Page of 61
48 Ceiling Cassette Air Conditioner
(3-way) Valve 
(3-way) Valve 
3-way Valve (Liguid Side)
3-way Valve (Gas Side)
Works
Shaft position
Shaft position
Service port
Shipping
Closed
Closed
Closed
(with valve cap)
(with valve cap)
(with cap)
Air purging
Open
Closed
Open
(Installation)
(counter-clockwise)
(clockwise)
(push-pin or with 
vacuum pump)
Operation
Open
Open
Closed
(with valve cap)
(with valve cap)
(with cap)
Pumping down
Closed
Open
Open
(Transfering)
(clockwise)
(counter-clockwise)
(connected 
manifold gauge)
Evacuation
Open
Open
Open
(Servicing)
(connected 
manifold gauge)
Gas charging
Open
Open
Open
(Servicing)
(with charging 
cylinder)
Pressure check
Open 
Open
Open
(Servicing)
(connected 
manifold gauge)
Gas releasing
Open
Open
Open
(Servicing)
(connected 
manifold gauge)
3.
2.
1.
4.
5.
6.
Valve cap
Open position
Closed position
Pin
Service 
port
Service 
port cap
To piping
connection
To outdoor unit
Valve cap
Open position
Closed position
Pin
Service 
port
Service 
port cap
To outdoor unit
To piping
connection
Service port
Closed
(with cap)
Open
(push-pin or with 
vacuum pump)
Closed
(with cap)
Closed
(with cap)
Closed
(with cap)
Open
(connected 
manifold gauge)
Open
(connected 
manifold gauge)
Open
(connected 
manifold gauge)