Trane SCIH User Manual

Page of 29
22
SXIH-SVX01B-EN
Maintenance
general
information
Table M-GI-1. Integral Air-Cooled General Data
Nominal Tons
5
7.5
10
15
ARI capacity - btu/h
60,600
91,000
121,900
177,200
(S)EER
10.47
1
10.36
10.38
9.76
R22 charge/circuit (lbs.)
9.2
14.3
9.3
11.7
Shipping weight – lbs.
908
1087
1495
1897
Operating weight – lbs.
848
1027
1445
1767
Compressor, qty - hp
1
1
2
2
Circuits
1
1
2
2
Condenser
Face area, sq/ ft.
6.74
10.75
16.55
16.55
Rows / fpf
4 / 180
4 / 168
3 / 180
4 / 180
Fans, qty.
1
1
2
2
Fan size, in.
15x15
15x15
15x15
15x15
Motor hp
1.5
2.0
2.0
5.0
Evaporator
Face area, sq. ft
5.99
8.32
12.82
12.82
Rows / fpf
4 / 144
4 / 144
4 / 144
4 / 144
Filter qty. - size, in.
2- 23.7x18
2 - 23.7x25
3 - 23.7x25.6
3 - 23.7x25.6
Fans qty. - size, in
1- 12x12
1 - 12x12
2 - 12x12
2 - 12x12
Motor hp
1.0
1.5
2.0
3.0
Min. airflow
1800
2700
3600
5400
Max. airflow
2200
3300
4400
6600
Notes: 1. Net cooling capacity is rated at 95°F ambient, 80°F entering dry bulb and 67°F entering wet bulb at scfm air
condition. 2. EER is rated at ARI conditions.
Footnote 1. SEER applies to 5-ton unit--ARI 210-240 Certified.