Installation - Mechanical
Important
1.
Additional glycol beyond the recommendations will adversely effect unit perfor-
mance. The unit efficiency will be reduced and the saturated evaporator tempera-
ture will be reduced. For some operating conditions this effect can be significant.
2.
If additional glycol is used, then use the actual % glycol to establish the low 
refrigerant cutout setpoint.
3.
The minimum low refrigerant cutout setpoint allowed is -5 deg F. The minimum is 
established by the solubility limits of the oil in the refrigerant.
Specials
The following constitute a special that must be calculated by engineering:
1.
Freeze inhibitor other than Ethylene Glycol or Propylene Glycol.
2.
Fluid delta T outside the range 4 to 16 deg F.
3.
Unit configuration other than Standard, Standard with extra pass, and Premium.
4.
% Glycol greater than maximum in column in 
Special should all be calculated by engineering. The purpose of calculating is to make 
sure that design saturation temperature is greater than 3 deg F. Additionally, the calcu-
lation must verify that the fluid freeze point is a minimum of 4 deg. F lower that the 
design saturation temperature. The low evaporator temperature cutout will be 4 deg F 
below the freeze point or -5 deg F, whichever is greater.