Installation - Mechanical 
 
Remote Evaporator Option
 WARNING
Hazard of Explosion! 
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do 
not use acetylene, oxygen or compressed air or mixtures containing 
them for pressure testing. Do not use mixtures of a hydrogen containing 
refrigerant and air above atmospheric pressure for pressure testing as 
they may become flammable and could result in an explosion. 
Refrigerant, when used as a trace gas should only be mixed with dry 
nitrogen for pressurizing units. Failure to follow these recommendations 
could result in death or serious injury or equipment or property-only 
damage.
For field evacuation, use a rotary-type vacuum pump capable of pulling a vacuum of 
500 microns or less. Follow the pump manufacturer's instructions for proper use of 
the pump. The line used to connect the pump to the system should be copper and be 
the largest diameter that can be practically used. A larger line size with minimum flow 
resistance can significantly reduce evacuation time.
Use the ports on the suction service valves and the liquid line shutoff valves for 
access to the system for evacuation. Ensure that the suction service valve, the liquid 
line shutoff valve, the oil line shutoff valve and any field installed valves are open in 
the proper position before evacuating.
Insulate the entire suction line and the suction accumulator line. Where the line is 
exposed to the weather, wrap it with weatherproof tape and seal with weatherproof 
compound.
Figure 29
Remote Evaporator