Trane RTAC 140-400 ton units (50 HZ) User Manual

Page of 252
126
RTAC-SVX01F-EN
Diagnostics
The following Diagnostic Table contains all diagnostics possible arranged 
alphabetically by the name assigned to each diagnostic. Not all diagnostics are 
available unless TechView is installed.
Legend to Diagnostics Table
Hex Code
: 3-digit code used to uniquely identify diagnostics.
Diagnostic Name: Name of the diagnostic as it appears at DynaView and/or 
TechView displays.
Severity: Defines the action of the above effect. Immediate means an instantaneous 
shutdown of the affected portion. Normal means routine or friendly shutdown of the 
affected portion. Special Mode means a particular mode of operation is invoked, but 
without shutdown, and Info means an Informational Note or Warning is generated.
Persistence: Defines whether or not the diagnostic and its effects are to be manually 
reset (Latched), or can be either manually or automatically reset (Nonlatched).
Criteria: Quantitatively defines the criteria used in generating the diagnostic and, if 
nonlatching, the criteria for auto reset.
Reset Level: Defines the lowest level of manual diagnostic reset command which can 
clear the diagnostic. The manual diagnostic reset levels in decreasing order of priority 
are: Local, Remote and Info. For example, a diagnostic that has a reset level of 
Remote, can be reset by either a remote diagnostic reset command or by a local 
diagnostic reset command, but not by the lower priority Info Reset command.
Hex 
Code
Diagnostic Name
 
and Source
Severity
Persis-
tence
Criteria
Reset 
 
Level
398
BAS Communication Lost
Special
NonLatch
The BAS was setup as "installed" at the MP and the Comm 3 LLID lost 
communications with the BAS for 15 contiguous minutes after it had 
been established. Refer to Section on Setpoint Arbitration to determine 
how setpoints and operating modes may be effected by the comm 
loss. The chiller follows the value of the Tracer Default Run Command 
which can be previously written by Tracer and stored nonvolatilely by 
the MP (either use local or shutdown).
Remote
390
BAS Failed to Establish 
Communication
Special
NonLatch
The BAS was setup as "installed" and the BAS did not communicate 
with the MP within 15 minutes after power-up. Refer to Section on 
Setpoint Arbitration to determine how setpoints and operating modes 
may be effected.  Note: The original requirement for this was 2 
minutes, but was implemented at 15 minutes for RTAC.
Remote
2E6
Check Clock
Info
Latch
The real time clock had detected loss of its oscillator at some time in 
the past. This diagnostic can be effectively cleared only by writing a 
new value to the chiller's time clock using the TechView or  DynaView's 
"set chiller time" functions.
Remote
8A
Chilled Water Flow (Entering 
Water Temperature)
Info
NonLatch
The entering evaporator water temp fell below the leaving evaporator 
water temp. by more than 2°F for 100 °F-sec.  For RTAC this diagnostic 
cannot reliably indicate loss of flow,  but can warn of improper flow 
direction through the evaporator,  misbound temperature sensors, or 
other system problems
Remote
5EF
Comm Loss: Chilled Water 
Flow Switch
Immediate
Latch
Continual loss of communication between the MP and the Functional 
ID has occurred for a 30 second period.
Remote
5F2
Comm Loss: Cond Rfgt 
Pressure, Circuit #1
Immediate
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
5F3
Comm Loss: Cond Rfgt 
Pressure, Circuit #2
Immediate
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
694
Comm Loss: Electronic 
Expansion Valve, Circuit #1
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
695
Comm Loss: Electronic 
Expansion Valve, Circuit #2
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
5DE
Comm Loss: Emergency 
Stop
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
68E
Comm Loss: Evap Oil Return 
Valve, Cprsr 1A
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
69E
Comm Loss: Evap Oil Return 
Valve, Cprsr 1B
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote
68F
Comm Loss: Evap Oil Return 
Valve, Cprsr 2A
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Remote