Trane RTAC 140-400 ton units (50 HZ) User Manual

Page of 252
142
RTAC-SVX01F-EN
Pre-Start Checkout
 WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects before 
servicing. Follow proper lockout/tagout procedures to ensure the power 
cannot be inadvertently energized. For variable frequency drives or other 
energy storing components provided by Trane or others, refer to the 
appropriate manufacturer’s literature for allowable waiting periods for 
discharge of capacitors. Verify with an appropriate voltmeter that all 
capacitors have discharged. Failure to disconnect power and discharge 
capacitors before servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of 
capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR 
3.
Connect the phase sequence indicator leads to the line Power terminal block, as 
follows:
4.
Turn power on by closing the unit supply power fused-disconnect switch.
5.
Read the phase sequence on the indicator. The “ABC” LED on the face of the 
phase indicator will glow if phase is “ABC.”
6.
If the “CBA” indicator glows instead, open the unit main power disconnect and 
switch two line leads on the line power terminal block(s) (or the unit mounted dis-
connect). Re-close the main power disconnect and recheck the phasing.
CAUTION
Compressor Damage!
Do not interchange any load leads that are from the unit contactors or 
the motor terminals. Doing so may damage the equipment.
7.
Reopen the unit disconnect and disconnect the phase indicator.
Water System Flow Rates
Establish a balanced chilled water flow through the evaporator. The flow rates should 
fall between the minimum and maximum values given on the pressure drop curves. 
Chilled water flow rates below the minimum values will result in laminar flow, which 
reduces heat transfer and causes either loss of EXV control or repeated nuisance, low 
temperature, cutouts. Flow rates that are too high can cause tube erosion in the evap-
orator.
Water System Pressure Drop
Measure water pressure drop through the evaporator at the field-installed pressure 
taps on the system water piping. Use the same gauge for each measurement. Do not 
include valves, strainers fittings in the pressure drop readings.
Pressure drop readings should be approximately those shown in the Pressure Drop 
Charts in the Mechanical Installation section.
Phase Seq. Lead 
Terminal
Black (Phase A)
L1
Red (Phase B)
L2
Yellow (Phase C)
L3