Trane RTAC 140-400 ton units (50 HZ) User Manual

Page of 252
78
RTAC-SVX01F-EN
Installation - Electrical
NOTE:
Exceptions are listed below.
When going from Stop to Auto, the EWP relay is energized immediately. If evaporator 
water flow is not established in 4 minutes and 15 sec., the CH530 de-energizes the 
EWP relay and generates a non-latching diagnostic. If flow returns (e.g. someone else 
is controlling the pump), the diagnostic is cleared, the EWP is re-energized, and 
normal control resumed.
If evaporator water flow is lost once it had been established, the EWP relay remains 
energized and a non-latching diagnostic is generated. If flow returns, the diagnostic is 
cleared and the chiller returns to normal operation.
In general, when there is either a non-latching or latching diagnostic, the EWP relay is 
turned off as though there was a zero time delay. Exceptions (see above table) 
whereby the relay continues to be energized occur with:
A Low Chilled Water Temp. diagnostic (non-latching) (unless also accompanied by an 
Evap Leaving Water Temperature Sensor Diagnostic)
or
A starter contactor interrupt failure diagnostic, in which a compressor continues to 
draw current even after commanded to have shutdown
or
A Loss of Evaporator Water Flow diagnostic (non-latching) and the unit is in the AUTO 
mode, after initially having proven evaporator water flow.
Alarm and Status Relay Outputs (Programmable Relays)
A programmable relay concept provides for enunciation of certain events or states of 
the chiller, selected from a list of likely needs, while only using four physical output 
relays, as shown in the field wiring diagram. The four relays are provided (generally 
with a Quad Relay Output LLID) as part of the Alarm Relay Output Option. The relay’s 
contacts are isolated Form C (SPDT), suitable for use with 120 VAC circuits drawing 
up to 2.8 amps inductive, 7.2 amps resistive, or 1/3 HP and for 240 VAC circuits 
drawing up to 0.5 amp resistive.
The list of events/states that can be assigned to the programmable relays can be 
found in 
. The relay will be energized when the event/state occurs.
Table 20
Pump Relay Operation
Chiller Mode
Relay Operation
Auto
Instant close
Ice Building
Instant close
Tracer Override
Close
Stop
TImed Open
Ice Complete
Instant Open
Diagnostics
Instant Open
Table 21
Alarm and Status Relay Output Configuration Table
Description
Alarm - Latching
This output is true whenever there is any active diagnostic that requires a manual reset to clear, that 
affects either the Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not 
include informational diagnostics.
Alarm - Auto Reset
This output is true whenever there is any active diagnostic that could automatically clear, that affects 
either the Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include 
informational diagnostics.
Alarm
This output is true whenever there is any diagnostic affecting any component, whether latching or auto-
matically clearing. This classification does not include informational diagnostics