Trane YSC060-120 User Manual

Page of 60
13
RT-PRC017-EN
General Data
Table GD-1 — General Data
Convertible Units
Convertible Units
Convertible Units
Convertible Units
Convertible Units
YSC060AD
YSC072AD
YSC090AD
YSC102AD
YSC120AD
Cooling Performance 
1
Gross Capacity - kW (MBh)
18.2 (62.0)
23.2 (79.0)
26.7 (91.0)
31.1 (106.0)
34.9 (119.0)
COP (EER) 
2
2.99 (10.2)
3.08 (10.5)
3.02 (10.3)
3.02 (10.3)
2.99 (10.2)
Nominal Airflow - m
3
/h (cfm)
3400 (2000)
4080 (2400)
5100 (3000)
5780 (3400)
6800 (4000)
Rated Airflow - m
3
/h (cfm)
3400 (2000)
3570 (2100)
4460 (2625)
5100 (3000)
5950 (3500)
Net Capacity - kW (MBh)
17.3 (59.0)
22.0 (75.0)
25.2 (86.0)
29.9 (102.0)
33.1 (113.0)
System Power - kW
5.78
7.14
8.35
9.9
11.08
Heating Performance 
3
Heating Models
Low - G80
High - G120
Low - G120 High G-200
Low - G120
High G-200
Low - G150 High G-250 Low - G150
High G-250
Heating Input - kW (MBH)
19.6 (67)
29.3 (100)
29.3 (100)
48.9 (167)
29.3 (100)
48.9 (167)
36.7 (125)
60.9 (208)
36.7 (125)
60.9 (208)
Heating Output - kW (MBH)
15.7 (54)
23.4 (80)
23.4 (80)
39.1 (134)
23.4 (80)
39.1 (134)
29.3 (100)
48.7 (166)
29.3 (100)
48.7 (166)
Steady State Efficiency %
90
90
90
90
90
90
90
90
90
90
No. Burners
2
3
3
4
3
4
3
5
3
5
No. Stages
1
1
1
2
1
2
2
2
2
2
Gas Connection Pipe Size - in.
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
3/4 NPT
Compressor
Number - Type
1-Climatuff Scroll
1-Trane 3-D Scroll
1-Trane 3-D Scroll
2-Climatuff Scroll
2-Climatuff Scroll
Outdoor Sound Rating dB 
4
80
85
85
83
79
Outdoor Coil - Type
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size in. OD
0.3125
0.3125
0.3125
0.3125
0.3125
Face Area - m
2
 (sq ft)
1.02 (10.96)
1.29 (13.88)
1.29 (13.88)
1.75 (18.89)
2.41 (25.92)
Rows / FPI
3 / 17
2 / 17
2 / 17
2 / 17
2 / 17
Indoor Coil - Type
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size OD - in.
0.3125
0.3125
0.3125
0.3125
0.3125
Face Area - m
2
 (sq ft)
0.62 (6.68)
0.92 (9.89)
0.92 (9.89)
1.15 (12.36)
1.15 (12.36)
Rows / FPI
3 / 16
2 / 16
3 / 16
3 / 16
4 / 16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Drain Connection No. / Size - in.
1 / 0.75 NPT
1 / 0.75 NPT
1 / 0.75 NPT
1 / 0.75 NPT
1 / 0.75 NPT
Outdoor Fan - Type
Propeller
Propeller
Propeller
Propeller
Propeller
No. Used / Diameter - in.
1 / 22
1 / 26
1 / 26
1 / 26
1 / 26
Drive Type / No. Speeds
Direct / 1
Direct / 1
Direct / 1
Direct / 1
Direct / 1
CFM
2900
5100
5200
5500
5800
No. Motors / kW (HP)
1 / 0.30 (0.40)
1 / .56 (0.75)
1 / .56 (0.75)
1 / .56 (0.75)
1 / .56 (0.75)
Motor RPM
950
950
950
950
950
Belt Drive Indoor Fan - Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
1
1
Fan Diameter x Width - mm (in.)
280 X 280 (11 x 11)
305 X 305 (12 x 12)
305 X 305 (12 x 12)
381 X 381 (15 x 15)
381 X 381 (15 x 15)
Drvie Type / No. Speeds
Belt / Variable Speed
Belt / Variable Speed
Belt / Variable Speed
Belt / Variable Speed
Belt / Variable Speed
No. Motors
1
1
1
1
1
Standard Motor Power - kW (HP)
1.1 (1.5)
1.1 (1.5)
1.5 (2.0)
1.5 (2.0)
2.2 (3.0)
Oversized Motor Power - kW (HP)
-
1.5 (2.0)
2.2 (3.0)
2.2 (3.0)
-
Motor RPM - Standard / Oversized
1450 / -
1450 / 1450
1450 / 2850
1450 / 2850
2850 / -
Motor Frame Size
56
56
56
56
56
Filters - Type Furnished
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
(No.) Size Reccommended - mm
(2) 508 X 762 X 25
(4) 406 X 635 X 50
(4) 406 X 635 X 50
(4) 508 X 635 X 50
(4) 508 X 635 X 50
(No.) Size Reccommended - in.
(2) 20 X 30 X 1
(4) 16 X 25 X 2
(4) 16 X 25 X 2
(4) 20 X 25 X 2
(4) 20 X 25 X 2
Refrigerant Charge - kg (lbs) of R-22 
5
3.7 (8.2)
3.7 (8.2)
4.5 (10.0)
Circuit 1 - 3.8 (8.3)
Circuit 1 - 3.4 (7.5)
Circuit 2 - 2.0 (4.4)
Circuit 2 - 3.3 (7.3)
Notes:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb.  Gross capacity does not include the effect of fan motor
heat.  Net capacity includes the effect of fan motor heat.  Units are suitable for operation to ± 20 % of nominal airflow.
2. EER are rated at ARI conditions.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. Outdoor Sound rating shown is tested in accordance with ARI Standard 270.  For more information refer to Performance Data Table "Sound Power Level".
5. Refrigerant charge is an approcimate value.  For a more precise value, see unit nameplate and service literature.