Thermo Products 30 User Manual

Page of 91
All installations and services must be performed by qualified service personnel. 
 
J.  Electrical Wiring 
 
: This appliance must be grounded in accordance with local 
codes, or in the absence of local codes, with the National Electrical Code, 
ANSI/NFPA 70-1999, or the latest edition. 
 
:  Waterproof type connectors must be used when connecting 
electrical power and control wiring to the unit to prevent moisture from 
being drawn into the unit during operation. 
 
All wiring must conform to the provisions of local codes or, in the absence of local 
codes, with the provisions of the National Electrical Code, ANSI/NFPA 70-1999, 
or the latest edition, and this instruction manual. 
 
This appliance requires 208-240 VAC, 60 Hz, single-phase power. Refer to Table 
5 for typical electrical current draws of the individual appliance motors, 
recommended sizes for over-current and short circuit devices, and minimum 
recommended field wiring sizes. Electrical service must be brought to the unit 
from a circuit breaker, or fused disconnect switch, in accordance with local 
codes. The disconnecting switch must be located reasonably close to and within 
sight of the unit.  
 
Three-wire service, two “hot” leads (L1 and L2) and a neutral (N), plus a ground 
conductor, is required. Connect power to the appliance control system at the 
junction box in the burner compartment. (A knockout fitting is provided on the 
exterior of the burner compartment for this purpose.) A ground wire must be 
connected to the grounding lug, or screw, marked “Equipment Ground”, in the 
junction box. 
 
Field wiring of power circuits to the appliance should consist of copper 
conductors rated for at least 240 VAC with an insulation temperature rating of at 
least 75
°C temperature rise. Depending upon code requirements, rigid or flexible 
conduit is recommended, and may be required. Connect the electric power 
supply as shown in the wiring diagram located on the inside of the burner 
compartment cover, or in this manual.  The cooling system operates on 208-240 
VAC electric power, from supply wires L1 and L2. The heating system operates 
on 120 VAC electric power, from supply wires L1 and N.  
 