Thermo Products 30 User Manual

Page of 91
All installations and services must be performed by qualified service personnel. 
 
86 
XV.   APPENDIX F: SPECIFICATION SHEETS 
Model No.:
OPB24-80
OPB30-80
OPB36-80
Heating Performance (using # 2 fuel oil):
Input rate (BTUH), Maximum / Minimum :
Heating capacity (BTUH), Maximum / Minimum : 
Design temp. rise (deg. F.) on LOW fan speed:
Burner nozzle & oil pressure for max. input rate:
Burner nozzle & oil pressure for min. input rate:
Cooling Performance:
Cooling capacity (tons):
2
2.5
3
Fan speed:
800
1000
1200
SEER
14
13
13
Refrigerant: 
Factory refrigerant charge (by weight, in ounces):
72
72
80
Nominal Electrical Power Requirements:
 208-240V / 60 Hz / 1 Ph. current (Amps):
18.7
24.9
27.8
Min. fuse or circuit breaker rating (Amps): 
30
30
40
Circulating Fan, Motor, & Air Filter:
Blower wheel design and size:
Airflow @ 0.4 in. W.G. external static pressure:
    High speed (SCFM):
    Medium-high speed (SCFM):
    Medium-low speed (SCFM):
    Low speed (SCFM):
Blower motor type & frame:
Nominal blower motor output (HP):
Blower motor full load current (Amps):
Number of blower speeds:
Maximum Rotation speed (RPM): 
Direction of rotation (from shaft end):
Motor housing diameter (in.):
Motor housing length (in.):
Shaft diameter (in.):
Shaft length (in.):
Filter type:
Number and size of air filters (in.): 
Dimensions & Weight:
Height of housing (in.):
Width of housing (in.):
Depth of housing (in.):
Supply air outlet, width (in.) x height (in.):
Return air inlet, width (in.) x height (in.):
Approx. shipping weight (including packaging, lbs):
610
0.60 GPH @ 120 PSIG, 80 deg., hollow cone type
HCFC-410A (R-410A)
105,000 / 85,000
85,000 / 68,000
65
0.75 GPH @ 130 PSIG, 80 deg., hollow cone type
Directly-driven, DWDI FC centrifugal, 12 in. O.D.
ECM, air-over, 48Y
3/4
1250
1090
970
800
9.6
Variable
1400
Clockwise
5.59
6.96
0.5
3.5
35
47
Permanent
1 - 20 x 25 
20 x 12
20 x 12
47