Vermont Casting MSZ-D36NA User Manual

Page of 36
18
EMERGENCY OPERATION switch
E.O.
SW
E.O.
SW
8-9. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor 
unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote 
controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at 
High speed and the system is in continuous operation (with thermostat ON).
After 30 minutes of test run operation the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of 
75 °F (24 °C). The fan speed shifts to Med.
All protective operations such as the coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO (
) mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any 
signal from the remote controller. In case of latter normal operation will start.
NOTE
 : Do not press EMERGENCY OPERATION switch during normal operation.
8-11. CHANGING TEMPERATURE INDICATION (°F /°C)
8-10. 3-MINUTE TIME DELAY OPERATION
When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect 
compressor from overload.
The preset unit is °F.
°F→°C : Press RESET button while the 
temperature buttons are pressed.
°C→°F : Press RESET button or remove 
the batteries .
Press RESET button gently using 
a thin stick.
Operation mode
COOL
HEAT
(MUZ)
Set temperature
75 °F (24 °C) 75 °F (24 °C)
Fan speed
Med.
Med.
Horizontal vane
Auto
Auto
The operation mode is indicated by the Operation 
Indicator lamp as following
Operation Indicator lamp
(MSZ type)
EMERGENCY COOL
 
EMERGENCY HEAT
 
STOP
  
(MSY type)
EMERGENCY COOL
 
STOP
 
 
 Lighted
 Not 
lighted