York YPAL 051 User Manual

Page of 168
26
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Installation
GENERAL ARRANGEMENT DRAWINGS (CONTINUED)
FIG. 2-4 – GENERAL ARRANGEMENT DRAWING (CONT.)
BOTTOM SUPPLY / SIDE RETURN
SECTION DESCRIPTIONS:
 EE = Economizer
FE = Fan Exhaust
_F = Filter Segments
CC = Cooling Coils
FS = Supply Fan
DP
 = Discharge Plenum
CO = Condenser Section
LD08370
6.28
38.37
49.94
4.79
GAS
BURNERS
GAS LINE CONNECTION 2-1/2" GAS OUTLET 1-1/2" MPT
 CONN.
195.38
221.00
GAS HEA
T
 FLUE
GAS HEA
T
 EXHAUST
 FLUE
FIELD INST
ALLED
102.62
T
O
P
 VIEW
REAR VIEW
SIDE VIEW
(LEFT
 SIDE)
FRONT
 VIEW
1.50
78.00 CLEAR
FOR COIL
 PULL
30.00 
DOOR
SWING 
CLEAR-
ANCE
BOTH 
SIDES
95.25
92.00
82.00
84.00 
CLEAR
91.00 
CLEAR
FOR COIL
PULL
120.00 CLEAR
339.00
AIRFLOW
106.00
1-1/4" FPT
 DRAIN
LEFT
 SIDE ONL
Y
170.31
ELECTRICAL
 SER
VICE
60.00 CLEAR
FOR AIR 
INT
AKE
BOTH SIDES
136.82
OA
OA
69.83
75.58
5.74
230.62
191.19
NOTES:
1.  10’
 clearance minimal over the top of the condensing unit.
2.  Only one adjacent wall can exceed unit height.
3.  12’
 clearance required to adjacent units.
4.  8’
 service access recommended on one side.
5.  Economizer and exhaust hoods, where applicable are folded inside unit for shipment.