York YPAL 051 User Manual

Page of 168
35
2
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
VAV Heat Relay Output
This is a 24 VDC output that is turned on when the 
unit is in the heating mode.  The fi eld can use this as 
a signal to trigger the opening of the VAV boxes for 
heating operation.  This feature uses two ¼ inch male 
tabs identifi ed as (VAV OPEN +) and (VAV OPEN -) 
on the Simplicity control board.
Supply Air Temperature Reset
An external 0 to 10 VDC input can be applied to 
terminals (REM+) and (REM-) at terminal block P19 
on the Simplicity control board to reset the supply air 
temperature set point for VAV operation.  The units 
follows interprets the voltage input as follows:
  
Below 1.0 VDC – the blower is de-energized
   Below 1.5 VDC – the cooling and heating is 
disabled
   At 2.0 VDC – the control uses the lower set 
point
  
Between 2.0 VDC and 10 VDC the change in set 
point is proportional to the change in voltage.
   At 10.0 VDC – the control uses the upper set 
point
COMMUNICATION
The Simplicity Unit Controller is designed to 
communicate using Modbus Client protocol.  Through 
the use of a ModLINC translator the unit can also 
communicate using BACnet MS/TP protocol.  
Through the use of a FREEnet Serial or USB adapter 
the Simplicity Unit Controller can be connected directly 
to a computer.  Multiple units can be daisy chained 
together and through the use of the adapter connected to 
a computer or a network.  This allows remote monitoring 
of the unit as well as the ability to change settings and 
options from a remote location.
Connection to the unit is done through either of two 
RS-485 connections.  The P4 terminal block has screw 
connections with terminal A being the – and terminal 
B being the +.  The P5 connecter is designed to allow 
the mating connector from the FREEnet Serial or USB 
adapter to be plugged in.
See Table 6-1 for parameter points list.
DIRTY FILTER SWITCH
On units with a dirty fi lter switch option, an adjustable 
differential pressure switch is installed to monitor the 
pressure drop across the fi lters.  When the pressure 
drop across the fi lters exceeds the setting of the switch, 
the switch closes sending a 24-volt signal to the Unit 
Controller.  The Unit Controller posts a warning in 
the service memory buffer; but will not shut down the 
unit.