  Intelli-Start will only work on a Constant Volume 
system using a space sensor.
  Intelli-Start will only work when the internal 
scheduling feature is used.  It will not work using 
a hard wired or communicated Occupied com-
mand.
  Intelli-Start will only function during the fi rst 
occupied period of each day.
Sequence of Operation
First day of heating or cooling operation
  Two hours prior to the start of the occupied period 
the Simplicity Control will compare the space 
temperature to the “CV OCCUPIED COOLING” 
or the “CV OCCUPIED HEATING” set points.
 Heating 
operation
–  If the space temperature is 1.5° F or more 
below the “CV OCCUPIED HEATING” set 
point the Simplicity Elite control will stage on 
the heat using the normal heating with space 
sensor logic.
–  The Simplicity Elite control will record the 
space temperature and how long it takes to 
bring the space temperature to the “CV OC-
CUPIED HEATING”
 set point.
– When the “CV OCCUPIED HEATING” set 
point is reached the Simplicity Elite control 
will divide the elapsed time into 5-minute 
increments.
–  The Simplicity Elite control will determine 
how many 0.1° F the temperature was below 
the “CV OCCUPIED HEATING” set point.
–  The Simplicity Elite control will then cal-
culate how many 0.1° F were satisfi ed  per 
5-minute increment.
–  This number will be recalculated each day.
–  The Simplicity Elite control also records the 
outdoor temperature when the above calcula-
tions are made.
 Cooling 
operation
–  If the space temperature is 1.5° F or more 
above the “CV OCCUPIED COOLING” set 
point the Simplicity Elite control will stage on 
cooling operation using the normal Cooling 
with space sensor logic.
–  The Simplicity Elite control will record the 
space temperature and how long it takes to 
bring the space temperature to the “CV OC-
CUPIED COOLING”
 set point.
– When 
the 
“CV OCCUPIED COO0LING” set 
point is reached the Simplicity Elite control 
will divide the elapsed time into 5-minute 
increments.
–  The Simplicity Elite control will determine 
how many 0.1° F the temperature was above 
the “CV OCCUPIED COOLING” set point
–  The Simplicity Elite control will then cal-
culate how many 0.1° F were satisfi ed  per 
5-minute increment.
–  This number will be recalculated each day.
–  The Simplicity Elite control also records the 
outdoor temperature when the above calcula-
tions are made.
Subsequent Operation
  Each morning two hours before the scheduled 
occupied start time the Simplicity Elite control 
looks at the space temperature and the “CV OC-
CUPIED COOLING”
 and “CV OCCUPIED 
HEATING”
 set points and determines if there is 
a need for cooling or heating operation.
  Based on which need is identifi ed the Simplicity 
Elite control will calculate the number of 0.1° 
F increments the space temperature is from set 
point and multiple this value time the previous 
days calculation on the number of 0.1° F the unit 
can satisfy in 5 minutes.  This will determine 
how many minutes prior to the beginning of the 
occupied period the control will need to start the 
heating or cooling operation.
  If cooling mode is selected the Simplicity Elite 
control will also compare the current outdoor 
temperature to the outdoor temperature recorded 
during the previous days start up period.
–  If the current outdoor air temperature is 
10.0° F or more above the previous day the 
Simplicity Elite control will add 5 minutes to 
the above calculated recovery time for every 
10.0° F difference.