York YPAL 050 User Manual

Page of 168
102
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
User Interface Control Center
ADDRESS
NUMBER
DESCRIPTION
UNITS OF ADJUSTMENT
RANGE OF 
ADJUSTMENT
CURRENT 
SETTING
36
OUTSIDE AIR HUMIDITY SENSOR INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
37
ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT
BTUS PER POUND
10 - 50
27
38
RETURN AIR HUMIDITY SENSOR INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
39
ECONOMIZER OUTSIDE AIR TEMP ENABLE 
SETPOINT
DEGREES F
40º - 80º
55º
40
DEMAND VENTILATION (IAQ) ENABLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
41
IAQ SENSOR RANGE
PARTS PER MILLION
0 - 5000 PPM
2000
42
IAQ SETPOINT
PARTS PER MILLION
0 - 5000 PPM
1000
43
POWER EXHAUST INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
ON
44
MODULATING POWER EXHAUST INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
45
EXHAUST VFD INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
46
EXHAUST DAMPER POSITION FOR EXHAUST FAN 
TO TURN ON (MODULATING ONLY)
PERCENT OF ECONOMIZER 
POSITION
0 - 100%
80%
47
EXHAUST DAMPER POSITION FOR EXHAUST FAN 
TO TURN OFF
PERCENT OF ECONOMIZER 
POSITION
0 - 100%
20%
48
ECONOMIZER DAMPER POSITION FOR EXHAUST 
FAN TO TURN ON (NON-MODULATING ONLY)
PERCENT OF ECONOMIZER 
POSITION
0 - 100%
60%
49
ECONOMIZER DAMPER POSITION FOR EXHAUST 
FAN TO TURN OFF (MODULATING ONLY)
PERCENT OF ECONOMIZER 
POSITION
0 - 100%
20%
50
APS  DATA
0 = CLOSED,
1 = OPEN
0 = CLOSED,
1 = OPEN
OPEN
51
DIRTY FILTER SWITCH INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
52
DIRTY FILTER SWITCH DATA
0 = CLOSED,
1 = OPEN
0 = OPEN,
1 = CLOSED
OPEN
53
COOLING MODE OPERATION ENABLE
PARAMETER BIT
0 = OFF, 1 = ON
ON
54
HEATING MODE ENABLED FOR OPERATION
PARAMETER BIT
0 = OFF, 1 = ON
ON
55
CONTINUOUS INDOOR FAN OPERATION WITH 
SENSOR
PARAMETER BIT
0 = OFF, 1 = ON
ON
56
SPACE TEMPERATURE OFFSET RANGE
DEGREES F
-5º F - 5º F
0º F
57
METRIC OPERATION
PARAMETER BIT
0 = OFF, 1 = ON
OFF
58
THIRD PARTY BAS ECONOMIZER ENABLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
59
YEAR
YEAR (BCD)
00 - 99
4
60
MONTH
MONTH
1 - 12
1
61
DAY OF MONTH
DAY OF MONTH
1 - 31
1
62
DAY OF WEEK
DAY OF WEEK
1 - 7
1
63
HOUR
HOURS
0 - 23
0
64
MINUTE
MINUTES
0 - 59
0
65
SUPPLY AIR TEMP
DEGREES F
-40º - 180º
0
66
RETURN AIR TEMP
DEGREES F
-40º - 180º
0
67
OUTSIDE AIR TEMP
DEGREES F
-40º - 180º
0
68
SPACE TEMP
DEGREES F
-40º - 180º
0
69
OUTSIDE AIR HUMIDITY
HUMIDITY
0% - 100%
0
70
RETURN AIR HUMIDITY
HUMIDITY
0% - 100%
0
71
OCCUPIED INPUT ENABLE
PARAMETER BIT
0 = OFF, 1 = ON
OFF
TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)
Continued on next page