User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS 
(HEX)
ADDRESS 
(DEC)
BIT
INITIAL/
DEFAULT 
VALUE 
(HEX)
MIN 
VALUE
MAX 
VALUE
DESCRIPTION
D7L
215 L
NA
0
 -
 -
OPTION BYTE #7
0
1 = ERV ENABLED
1
1 = ERV UNOCCUPIED FAN ENABLED
2-7
NA
D8 H
216 H
S
0
100
HOT GAS REHEAT HUMIDITY SETPOINT (PERCENT HUMIDITY)
D8 L
216 L
50
20
80
TEMPERATURE / HUMIDITY SETPOINT (PERCENT HUMIDITY)
D9 H
217 H
3
0
5
MAXIMUM TEMPERATURE / HUMIDITY OFFSET (DEGREES F)
D9 L
217 L
5
1
10
TEMPERATURE / HUMIDITY VALUE THAT = 1° F OF OFFSET 
(PERCENT HUMIDITY)
DB H
219 H
72
45
99
OPERATING COOLING SETPOINT (DEGREES F)  [CV]
DB L
219 L
68
45
99
OPERATING HEATING SETPOINT (DEGREES F)  [CV]
DC H
220 H
-
10
50
OUTSIDE AIR ENTHALPY (BTUS PER POUND)
DC L
220 L
-
10
50
RETURN AIR ENTHALPY (BTUS PER POUND)
DE L
222 L
50
0
100
MAXIMUM DEMAND VENTILATION ECONOMIZER POSITION 
(PERCENT OPEN)
DF H
223 H
-
0
10
SPACE SENSOR OFFSET (0 = -5° F, 10 = +5° F)
E0 H
224 H
-
-
-
ASCD TIMER FOR HEATING STAGE #1 (SECONDS, COUNTS 
DOWN)
E0 L
224 L
-
-
-
HEATING STAGE #1 MINIMUM RUN TIMER (SECONDS, COUNTS 
DOWN)
E1 H
225 H
-
-
-
ASCD TIMER FOR HEATING STAGE #2 (SECONDS, COUNTS 
DOWN)
E1 L
225 L
-
-
-
HEATING STAGE #2 MINIMUM RUN TIMER (SECONDS, COUNTS 
DOWN)
E2 H
226 H
-
-
-
ASCD TIMER FOR HEATING STAGE #3 (SECONDS, COUNTS 
DOWN)
E2 L
226 L
-
-
-
HEATING STAGE #3 MINIMUM RUN TIMER (SECONDS, COUNTS 
DOWN)
E3 H
227 H
0
0
99
LOW AMBIENT ECONOMIZER MINIMUM POSITION (PERCENT)
E3 L
227 L
0
0
60
LOW AMBIENT ECONOMIZER SETPOINT (DEGREES F)