York YPAL 050 User Manual

Page of 168
153
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
8
ANALOG INPUT OPERATION
This section describes the control operation of the (29) 
twenty-nine analog inputs.  These inputs are used by 
the control to monitor and respond to unit temperatures, 
pressures, enthalpy, etc.  The location of each of these 
connections on the Unit Controller is contained in 
Table 8-8.  Notice that the ID gives the jack connection 
designated as “J” and then the identifying number of 
the connector, followed by a – and then the pin number 
of the connector.  For example the SUPPLY AIR 
TEMPERATURE analog input would be found at J1-1.  
This is connector J1 – Pin 1.  As the Unit Control board 
is positioned in the control box the top row of the J series 
connectors is the input, the middle row is the common, 
and the bottom row is the 5 VDC input to the sensor.  
Also the pin in the right hand top corner is pin 1.
Temperature Sensors
The temperature sensors are all 10K Type III Thermistors.  
The relationship between the temperature and the 
voltage output and resistance is contained in Table 8-1 
.The following analog input are of this type:  Supply 
Air Temperature, Heat Entering Temp, Flex Evap Temp, 
Outside Air Temp, Return Air Temp, Suction Temp #1, 
Suction Temp #2, Zone Temp, and Under Floor Temp.
Duct Pressure Transducer
The Duct Pressure Transducer is located behind the right 
hand damper door.  The purpose of the transducer is to 
sense and convert the static pressure in the supply-side 
of the duct to a 0 to 5 volt DC voltage.  The DC voltage 
is sent to the Unit Controller and compared against the 
“DUCT STATIC PRESS ACTIVE SP”.  The transducer is 
factory wired, but pneumatic tubing must be fi eld supplied 
and installed (refer to Section 2 “INSTALLATION” in this 
manual).
  The Duct Static Pressure Transducer measures 
differential pressure between the pressure in the duct 
and atmospheric pressure.  When verifying transducer 
operation, the technician must insert a tee in the pneumatic 
tubing and connect a manometer to the tee to verify the 
pressure being applied to the transducer.  Once this pressure 
is known, a comparison can be made of the duct pressure 
vs. output volts DC from the transducer.  Table 8-2 shows 
the relationship between the pressure applied to the duct 
pressure transducer and the output voltage.  The output is 
linear between 0" WC and the SPAN.  The “DUCT PRESS 
TRANSDUCER SPAN”
 can be set to 1.25, 2.5 or 5" WC.
The “DUCT PRESS TRANSDUCER SPAN” must always 
be set based on the span of the transducer installed.
°F
VOLTAGE
RESISTANCE
°C
-25
0.49
139,639
-30.6
-20
0.53
127,453
-28.9
-15
0.60
109,624
-26.1
-10
0.69
94,519
-23.34
-5
0.78
81,665
-20.55
0.0
0.88
70,750
-17.78
5
0.98
61,418
-15.00
10
1.10
53,426
-12.22
15
1.22
46,582
-9.44
20
1.35
40,703
-6.67
25
1.48
35,639
-3.89
30
1.62
31,269
-1.11
35
1.77
27,490
1.67
40
1.91
24,219
4.44
45
2.06
21,377
7.22
50
2.21
18,900
10.00
TABLE 8-1 – TEMPERATURE SENSOR RESISTANCE
°F
VOLTAGE
RESISTANCE
°C
55
2.36
16,744
12.78
60
2.51
14,681
15.56
65
2.66
13,216
18.33
70
2.80
11,771
21.11
75
2.94
10,502
23.89
80
3.08
9,388
26.67
85
3.21
8,404
29.45
90
3.33
7,537
32.22
95
3.45
6,770
35.0
100
3.56
6,090
37.78
105
3.66
5,487
40.56
110
3.76
4,951
43.34
115
3.85
4,475
46.11
120
3.94
4,050
48.89
125
4.02
3,671
51.66
130
4.09
3,332
54.44
135
4.16
3,029
57.22
SECTION 8 – SERVICE