York YPAL 050 User Manual

Page of 168
65
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
5
Occupied Heating
There are three stages of heating available:
  W1 – First Stage of Heating 
  W2 – Second Stage of Heating 
  W3 – Third Stage of Heating
See the Heating section of this manual for a description 
of the heating staging.
Unoccupied Heating
Unoccupied heating operation is the same as Occupied.  
A programmable thermostat would be required in order 
to change the heating temperature settings between 
occupied and unoccupied.
Space Sensor – Hard Wired or Communicated
The following System Parameters must be programmed 
through the Simplicity Control:
  “CV OCCUPIED COOLING SETPOINT” – us-
ing Parameter 10 under the PROGRAM key on 
the Simplicity control board or under the COOL-
ING SETUP tab in the Simplicity PC software 
package.
  “CV OCCUPIED HEATING SETPOINT” – us-
ing Parameter 11 under the PROGRAM key on 
the Simplicity control board or under the HEAT-
ING SETUP tab in the Simplicity PC software 
package.
  “CV UNOCCUPIED COOLING SETPOINT” 
– using Parameter 12 under the PROGRAM 
key on the Simplicity control board or under 
the COOLING SETUP tab in the Simplicity PC 
software package.
  “CV UNOCCUPIED HEATING SETPOINT” 
– using Parameter 13 under the PROGRAM 
key on the Simplicity control board or under 
the HEATING SETUP tab in the Simplicity PC 
software package.
Cooling Operation – Occupied or Unoccupied
The Simplicity Control will stage on the cooling as 
follows:
  At cooling start up
–  If the space temperature is between 1.5° F and 
1.9° F above the “CV OCCUPIED COOLING 
SETPOINT”
 or “CV UNOCCUPIED COOL-
ING SETPOINT”
 the control will turn on the 
fi rst compressor from System 1 and turn on a 
5 minute timer.
–  If after 5 minutes the space temperature is 
between 1.5° F and 1.9° F above the “CV 
OCCUPIED COOLING SETPOINT”
 or “CV 
UNOCCUPIED COOLING SETPOINT”
 the 
control will bring on the second compressor 
of System 1 and start a 5-minute timer.
 OR
–  If the space temperature is greater than 2.0° F 
or more above the “CV OCCUPIED COOL-
ING SETPOINT”
 or “CV UNOCCUPIED 
COOLING SETPOINT”
 the control will bring 
on the fi rst compressor from System 1 and 
start a 3 minute timer.  After 30 seconds, the 
control will bring on the second compressor 
from System 1.
  If after 3 or 5 minutes the space temperature is 
between 1.5° F and 1.9° F above the “CV OC-
CUPIED COOLING SETPOINT”
 or “CV UN-
OCCUPIED COOLING SETPOINT” 
the control 
will bring on the fi rst compressor from System 2 
and start a 5 minute timer.
  If after 3 or 5 minutes the space temperature 
is 2.0° F or more above the “CV OCCUPIED 
COOLING SETPOINT”
 or “CV UNOCCUPIED 
COOLING SETPOINT”
 the control will bring 
on the fi rst compressor of System 2 and start a 3 
minute timer.
  If after 3 or 5 minutes the space temperature 
is 1.5° F or more above the “CV OCCUPIED 
COOLING SETPOINT” 
or “CV UNOCCUPIED 
COOLING SETPOINT”
 the control will bring on 
the second compressor of System 2.