FORM 100.50-NOM6 (1207)
5
–  The Simplicity Control uses the temperature 
difference calculated when the first com-
pressor was turned on to verify the supply 
air temperature will not drop 5.0° F or more 
below the cooling “VAV COOLING SUPPLY 
TEMP UPPER   SAT SETPOINT”
 or “VAV 
COOLING SUPPLY AIR TEMP LOWER 
SETPOINT”.
  If turning a compressor on 
would result in the specifi ed drop in supply 
air temperature, the second compressor will 
not be turned on.
  The same logic will be used to stage on compres-
sor 3 and 4.
The Simplicity Control turns off compressor operation 
as follows:
  The supply air temperature is 5.0° F or more 
below the “VAV COOLING SUPPLY TEMP 
UPPER   SAT SETPOINT”
 or “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT”
. 
  It has been more than 5-minutes since the last 
compressor was turned on.
  The compressors will be turned off in the reverse 
order they were turned on.
Cooling – Unoccupied with Thermostat
The operation is the same as Occupied Cooling with a 
Thermostat except:
  A Y1 call will energize the supply fan.
  The Simplicity Control will not bring on compres-
sors until the supply air temperature is 5.0° F or 
more above the “VAV COOLING SUPPLY TEMP 
UPPER SAT SETPOINT”
 or “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT”.
  Both of the above criteria must be met before the 
Simplicity Control will bring on compressors.
Occupied or Unoccupied Heating with a Thermo-
stat
The following parameter must be programmed through 
the Simplicity Control:
  “VAV OCCUPIED HEATING ENABLED” 
– must be turned on using Parameter 26 under 
the PROGRAM key on the Simplicity control 
board or under the HEATING SETUP tab in the 
Simplicity PC software package.
Any W thermostat input will energize all the available 
heat stages with a 30 second delay between stages. 
Occupied Cooling with Hard Wired or Communi-
cated Space Sensor
The following System Parameters must be programmed 
through the Simplicity Control for VAV operation with 
a space sensor:
  “VAV COOLING SUPPLY AIR TEMP UPPER   
SETPOINT” – using Parameter 23 under the 
PROGRAM key on the Simplicity control board 
or under the COOLING SETUP tab in the Sim-
plicity PC software package.
  “VAV COOLING SUPPLY AIR TEMP LOWER   
SETPOINT” – using Parameter 24 under the 
PROGRAM key on the Simplicity control board 
or under the COOLING SETUP tab in the Sim-
plicity PC software package.
  “VAV SUPPLY AIR TEMP RESET SETPOINT” 
– using Parameter 25 under the PROGRAM 
key on the Simplicity control board or under 
the COOLING SETUP tab in the Simplicity PC 
software package.
The Simplicity Control will control the operation of the 
compressors as follows:
  If the space temperature is 2.0° F or more above the 
“VAV SUPPLY AIR TEMP RESET SETPOINT” 
the control will use the “VAV COOLING SUPPLY 
AIR TEMP LOWER SETPOINT”
.
  If the space temperature is not 2.0° F or more 
above the “VAV SUPPLY AIR TEMP RESET 
SETPOINT”
 the control will use the “VAV 
COOLING SUPPLY AIR TEMP UPPER 
SETPOINT”.
  If the control is using the “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT” per 
above the space temperature must be equal to or 
less than the “VAV SUPPLY AIR TEMP RESET 
SETPOINT”
 before the control would switch to 
the “VAV COOLING SUPPLY AIR TEMP UP-
PER SETPOINT”
.
  The control uses a 5-degree dead band around the 
cooling “VAV COOLING SUPPLY AIR TEMP 
UPPER SETPOINT”
 or “VAV COOLING SUP-
PLY AIR TEMP LOWERT SETPOINT”
.