York YPAL 050 User Manual

Page of 168
89
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
5
HYDRONIC HEAT
The following parameters must be programmed to use 
Hydronic Heat:
“HEATING MODE ENABLED FOR OPERATION” 
must be enabled using Parameter 54 under the 
PROGRAM key of the Simplicity Elite control board 
or under the HEATING SETUP tab in the Simplicity 
PC software package.
“HYDRONIC HEATING ENABLED” must be enabled 
using Parameter 18 under the PROGRAM key of the 
Simplicity Elite control board or under the HEATING 
SETUP tab in the Simplicity PC software package.
“HYDRONIC HEATING STAGE #1 SUPPLY AIR 
SETPOINT”
 must be programmed using Parameter 
19 under the PROGRAM key of the Simplicity Elite 
control board or under the HEATING SETUP tab in 
the Simplicity PC software package.
“HYDRONIC HEATING STAGE #2 SUPPLY AIR 
SETPOINT”
 must be programmed using Parameter 
20 under the PROGRAM key of the Simplicity Elite 
control board or under the HEATING SETUP tab in 
the Simplicity PC software package.
Sequence of Operation
On Constant Volume units whenever there is a call for 
the 1st stage of heating operation the Simplicity Elite 
control will vary a 2 to 10 VDC output to the hydronic 
valve to try and maintain the supply air temperature to 
within +/- 1.0° F of the “HYDRONIC HEATING STAGE 
#1 SUPPLY AIR SETPOINT”
.  The output to the valve 
can be found at terminal “HWV+” and “HWV-“ at 
connector P14 on the Simplicity Elite control board.
On Constant Volume units whenever there is a call for 
the 2nd stage of heating operation the Simplicity Elite 
control will vary a 2 to 10 VDC output to the hydronic 
valve to try and maintain the supply air temperature to 
within +/- 1.0° F of the “HYDRONIC HEATING STAGE 
#2 SUPPLY AIR SETPOINT”
.
On a VAV unit whenever there is a call for heat the 
Simplicity Elite control will vary the 2 to 10 VDC output 
to the hydronic valve to try and maintain the supply 
air temperature to within ±1º F of the “HYDRONIC 
HEATING STAGE #2 SUPPLYAIR SETPOINT”
The normal output to the valve is 2 VDC for 0% opening 
of the hydronic valve and 10 VDC for 100% opening of 
the hydronic valve.  If the following is enabled:
“HYDRONIC HEAT ACTUATOR VALVE REVERSE 
ACTING”
 must be enabled using Parameter 21 under 
the PROGRAM key of the Simplicity Elite control board 
or under the HEATING SETUP tab in the Simplicity 
PC software package.
Under this condition, the normal output to the valve is 
10 VDC for 0% opening of the hydronic valve and 0 
VDC for 100% opening of the hydronic valve.
HYDRONIC HEAT FREEZE STAT
All hydronic heat units are equipped with a freeze stat 
that monitors the temperature of the return air. The 
switch action is normally closed and opens when the 
return air temperature is less the 40.0º F. The 24 VAC 
signal to the freeze stat originates at terminal FSP on 
the control board. The 24 VAC input from the freeze 
stat enters the control at the FSI terminal.
When the freeze stat input is lost, the Simplicity Control 
will send a 10 VDC signal to the valve (direct acting), 2 
VDC (reverse acting) to open the valve. The valve will 
continue to drive open for 5 minutes, even if the freeze 
stat circuit remakes. If the freeze stat circuit closes and 
the 5 minute timing has expired, the unit will return to 
normal operation.
If the supply fan is operating and the outdoor damper 
is open the Simplicity Control will close the damper 
during the above sequence.
VENTILATION
The unit can be ordered / programmed for the following 
ventilation options:
 None.
 Manual.
  Fixed Minimum – Economizer option required.
  Demand Ventilation – Economizer option re-
quired.