FORM 100.50-NOM6 (1207)
5
Sequence of Operation
When the building static pressure is 0.015” WC or more 
above the “BUILDING PRESSURE SETPOINT” the 
Simplicity Elite control closes the output to the exhaust 
fan motor.  The output is at the “EXH” terminal of the 
P13 connector.
When the building static pressure is 0.015” WC or more 
below the “BUILDING PRESSURE SETPOINT” the 
Simplicity Elite control opens the output to the exhaust 
fan motor.
The minimum run time is 10 seconds and the minimum 
off time is 60 seconds.
Modulating Damper with Fixed Speed Exhaust
This exhaust option uses a standard motor without any 
type of speed control and a modulating damper.
The following System Parameters must be programmed 
through the Simplicity Elite control:
“POWER EXHAUST INSTALLED” – must be turned 
on using Parameter 43 under the PROGRAM key 
on the Simplicity Elite control board or under the 
ECONOMIZER/EXHAUST tab in the Simplicity PC 
software package.
“ B U I L D I N G   S TAT I C   P R E S S U R E   S E N S O R 
INSTALLED” 
– must be turned on using Parameter 85 
under the PROGRAM key on the Simplicity Elite control 
board or under the EQUIPMENT INSTALLATION tab 
in the Simplicity PC software package.
“BUILDING PRESSURE SETPOINT” must be 
programmed using Parameter 31 under the PROGRAM 
key on the Simplicity Elite control board or under the 
ECONOMIZER/EXHAUST tab in the Simplicity PC 
software package.
“MODULATING POWER EXHAUST INSTALLED” 
must be turned on using Parameter 44 under the 
PROGRAM key on the Simplicity Elite control board 
or under the ECONOMIZER/EXHAUST tab in the 
Simplicity PC software package.
“EXHAUST DAMPER POSITION FOR EXHAUST FAN 
TO TURN ON”
 must be programmed using Parameter 
46 under the PROGRAM key on the Simplicity Elite 
control board or under the ECONOMIZER/EXHAUST 
tab in the Simplicity PC software package.
“EXHAUST DAMPER POSITION FOR EXHAUST FAN 
TO TURN OFF”
 must be programmed using Parameter 
47 under the PROGRAM key on the Simplicity Elite 
control board or under the ECONOMIZER/EXHAUST 
tab in the Simplicity PC software package.
Sequence of Operation
When the building static pressure is 0.025” WC or more 
above the “BUILDING PRESSURE SETPOINT” the 
Simplicity Elite control sends a 2 to 10 volt DC signal to 
open the exhaust damper.  The output is at the “EXD+” 
and “EXD-“ terminals at the P14 connector.
When the exhaust damper position is equal to or greater 
than the “EXHAUST DAMPER POSITION FOR 
EXHAUST FAN TO TURN ON”
 the Simplicity Elite 
control turns on the exhaust fan.  The output is at the 
“EXH” terminal of the P13 connector. 
When the building static pressure is 0.025” WC or more 
below the “BUILDING PRESSURE SETPOINT” the 
Simplicity Elite control lowers the 2 – 10 volt DC output 
to the exhaust damper to close the damper.
When the exhaust damper position is equal to or less 
than the “EXHAUST DAMPER POSITION FOR 
EXHAUST FAN TO TURN OFF”
 the Simplicity Elite 
control turns on the exhaust fan.  
The minimum run time is 20 seconds and the minimum 
off time is 60 seconds.
Modulating Exhaust with a VFD
This exhaust option uses a Variable Frequency Drive 
(VFD) and a barometric damper.
The following System Parameters must be programmed 
through the Simplicity Elite control:
“POWER EXHAUST INSTALLED” – must be turned 
on using Parameter 43 under the PROGRAM key 
on the Simplicity Elite control board or under the 
ECONOMIZER/EXHAUST tab in the Simplicity PC 
software package.