York YCJF24 THRU 60 User Manual

Page of 28
413437-YTG-E-0909
Johnson Controls Unitary Products
3
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting 
line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data 
Table.
4. For TXV match charge weight needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator 
+ adder for line set.
System Charge for Various Matched Systems
Outdoor Unit 
YCJF24S41S1
YCJF30S41S1
YCJF36S41S1
YCJF42S41S1
YCJF48S41S1
YCJF60S41S1
Required Orifice or TXV 
1
1TVM4F1
1TVM4G1
1TVM4G1
1TVM4G1
1TVM4J1
1TVM4J1
Factory Charge, lbs-oz
3 - 2
3 - 7
3 - 10
4 - 4
4 - 9
5 - 9
Indoor Coil
2,3,4
Additional Charge, oz
FC/MC/PC24
10
FC/MC/PC30
10
2
FC/MC/PC35
16
10
FC/MC/PC36
10
4
5
FC/MC/PC37
24
19
15
FC/MC/PC43
24
19
15
5
FC/MC/PC48
40
32
27
17
16
FC/MC/PC60
17
16
0
FC/MC62
25
26
18
FC64
30
33
25
UC24
8
UC60
12
HC30
10
HC36
16
11
8
HC42
25
19
15
6
HC60
0
0
0
HD24
16
HD36
18
HD48
51
42
36
24
25
HD60
24
24
AHP30
16
AHP36
19
15
AHX30
16
11
AHX36
11
15
AHX42
31
27
17
AHX48
31
27
17
16
AHX60
33
22
23
18
AHP/SHP60
1
AV*24
3
AV*36
25
19
15
AV/SV*48
9
0
1
AV/SV*60
0
1
0
F4FP030
3
F4FP036
5
F4FP040
8
F4FP042
8
F4FP045
9
F5FP048
20
10
11
F5FP060
20
10
11
F4FV060
9
10
1
F6FP030
17
11
F6FP036
11
8
F6FP042
23
19
17
F6FP048
23
19
17
16
F6FP060
33
23
23
18
FOOTNOTES:
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3. A TXV kit must be used with these coils to obtain system performance. Note: If a TXV is factory installed on the coil, it must be replaced with 
the listed TXV.
4. Refer to Technical Guide for actual system performance for specified matches.