MAINTENANCE
MOTOR
The blower motor should be cleaned annually and if it 
has oiling ports, it should be oiled with a good grade of 
SAE 20 oil. Normally a few drops of oil in each bearing 
is sufficient.
If  motor  service 
is 
required, 
it 
can  be  removed 
in  the 
following manner:
  1.  Disconnect electrical power to 
the 
unit at 
the 
discon-
nect switch and lock out.
  2.  Remove two screws, securing blower deck 
to 
unit.
  3.  Locate motor lead wires where they connect 
to 
the 
side panel, (lower rear on the electrical box side).
  4.  The quick connect plug needs 
to 
be squeezed on top 
and bottom to release 
it 
from 
its 
socket (dual motor 
units 
have two plugs).
  5.  Now slide blower / motor deck out of 
unit to ser-
vice.
  6.  Reverse process to install.
COIL
The coil must be kept clean by any of the following 
methods.
 1.  Cleaning with low-pressure compressed air.
 2.  Flushing or rinsing with water (a detergent is ad-
visable for greasy surfaces).
 3.  Prior to the water system start-up and balancing, the 
chilled/hot water systems should be flushed to clean 
out dirt and debris, which may have accumulated 
during construction. All unit service valves are to 
be closed during this process. Strainers are to be 
installed in the piping mains to prevent this material 
from entering the units during normal operation.
FILTERS
Clean or Replace Air Filters Regu-
larly
The  intervals  at  which  filters  require  replacement 
depend on local conditions.
Because of dust and lint in the room, room-air filters load 
up much more rapidly than outdoor-air filters.  Under 
normal conditions, the room air filter requires cleaning 
every six to eight weeks.
The filter is a permanent type and may be removed and 
washed with a garden hose.  Filter should be completely 
dry before reinstalling.  To remove the filter, rotate the 
retaining rod holding the front edge of the filter so it 
can drop below the front panel of the cabinet, then pull 
outward to remove.  To reinstall the filter, slide the filter 
into the filter channels on both sides of the unit.  Rotate 
filter retaining rod on lower front edge of cabinet door 
so that it is under the filter, then push the rod upward 
into the cabinet door.
To ensure proper maintenance of the filters, it is best 
to follow an organized maintenance procedure.  The 
following one is recommended:
Divide the total number of units on the job into six 
equal groups.  Each week inspect, clean or replace the 
filters in each group, in rotation.  This insures a uniform 
servicing interval.  The interval may be lengthened or 
shortened as determined by experience.  If inspection 
shows only the room-air filter to be dirty, this one alone 
should be replaced.
Dirty filters reduce the air and heating 
capacities of the Unit.  When the filters 
are excessively dirty, the unit heating 
capacity will be so reduced that it is in-
effective for heating the room.  When 
a room fails to heat, always check the 
filters.
CLEAN UNIT INTERIOR
Once  a  year  clean  the  fans  and  coils  of  the  unit 
thoroughly.  Remove the access panel as necessary.
Wipe the interior of the unit clean with a rag.  Wipe the 
motor and inside and outside of the fan housings.  (In 
cooling units, clean out the drain pan.)