York ND480 User Manual

Page of 38
628767-YTG-C-0910                                                                                                                                                                                                                                  
18
Johnson Controls Unitary Products
ND360, 480 & 600 Drive Kit Data
UNIT MODEL
DRIVE KIT
 MODEL 
NUMBER
BLOWER
RPM 
RANGE
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
BELTS
PITCH DIA.
 (IN.)
BORE
 (IN.)
PITCH DIA.
 (IN.)
BORE 
(IN.)
QTY.
PITCH
 LENGTH
 (IN.)
DESIGNATION
ND360
1LD0415
636 - 795
4.0 - 5.0
1 3/8
11.0
1  3/16
2
63.3
A62
1LD0407
668 - 827
4.2 - 5.2
1 3/8
11.0
1  3/16
2
63.3
A62
1LD0408
827 - 986
5.3 - 6.3
1 3/8
11.0
1  3/16
2
59.7
A59
ND480
1LD0409
607 - 776
4.3 - 5.5
1 3/8
12.4
1  3/16
2
85.1
B84
1LD0410
776 - 917
5.4 - 6.6
1 3/8
12.4
1  3/16
2
86.8
B85
ND600
1LD0411
692 - 833
4.8 - 6.0
1 3/8
12.4
1  3/16
2
78.6
B78
1LD0412
762 - 931
5.4 - 6.6
1 5/8
12.4
1  3/16
2
76.8
B75
ND360, 480 & 600 Motor Kit Data
UNIT MODEL
HP
MOTOR KIT MODEL NUMBER
FRAME SIZE
VOLTAGE 
(3PH-60-HZ)
ND360
5.0
2LR04605023
184
208/230/460
2LR04605032
208/230/460
2LR04605158
575
7.5
2LP04607133
213
208/230/460
2LP04607158
575
10
2LP04610133
215
208/230/460
2LP04610158
575
ND480
7.5
2LP04607133
213
208/230/460
2LP04607158
575
10
2LP04610133
215
208/230/460
2LP04610158
575
ND600
10
2LP04610133
215
208/230/460
2LP04610158
575
15
2LP04615133
254
208/230/460
2LP04615158
575
ND360, 480 & 600 Motor Overload Elements
1
1
These units are equipped from the factory with a correctly 
sized motor starter; overload elements are not factory 
supplied. Three elements required per unit.
MOTOR HP
VOLTAGE
MODEL NUMBER
5
208
2MP04704600
230
2MP04704600
460
2MP04704900
575
2MP04705000
7.5
208
2MP04703700
230
2MP04704500
460
2MP04704300
575
2MP04704000
10
208
2MP04701600
230
2MP04704100
460
2MP04704200
575
2MP04704300
15
208
2MP04704400
230
2MP04701700
460
2MP04704500
575
2MP04704600