York YVC User Manual

Page of 12
5
YORK INTERNATIONAL
INSTALLATION
FORM 115.20-NOM3 (1006)
H
L (L1)
N (L2)
P OWE R
S UP P LY
G R D
1
2
3
4
1
2
3
4
T B 1-1 T B 1-2
T B 3-1
T B 3-2
T B 2-2
T B 2-4
T B 2-3
T B 1-4 TB 2-1
HE AT
OF F
C OOL
ME D
HI
HE AT
C OOL
LO
T B 3-3
T B 2-5
MOT OR
C
V ALV E S
T HE R MIS T OR
(UNIT -MT D)
T B 1-1 T B 1-2
T B 3-1
T B 2-2
T B 3-2
T B 2-3 T B 2-4 T B 1-4 T B 2-1
T B 3-3
OF F
C OOL
ME D
HI
LO
L1
ON
HE AT
T B 2-5
H
L (L1)
N (L2)
P OWE R
S UP P LY
G R D
1
2
3
4
1
2
3
4
MOT OR
C
V ALV E S
FIG. 4 - MANUAL CHANGEOVER,
 
CONTINUOUS FAN, T420 THERMOSTAT.
FIG. 5 - AUTO CHANGEOVER,
 
CONTINUOUS FAN, T421 THERMOSTAT.
4-PIPE HEAT / COOL
LDO6891
LDO6892
PIPING
These units employ a hydronic coil designed for use 
with either hot or chilled water. 
All piping must be adequately sized to meet the design 
water flow requirements as specified for the specific 
installation. Piping must be installed in accordance with 
all applicable codes. 
PIPE SIZES
  •  Tubing connections are 5/8" OD on all models.
  •  Manual  air  vents  are  provided  standard  on  all 
coils.
  •  All chilled water piping must be insulated to prevent 
condensation.
PRECAUTIONS
 1.  Flush all field piping prior to connection to remove 
all debris.
 2.  Use  wet  cotton  rags  to  cool  valve  bodies  when 
soldering.
 3.  Open all valves (mid-way for hand valves, manually 
open on motorized valves) prior to soldering.
 4.  When soldering to bronze or brass, heat the pip-
ing while in the socket/cup and begin introducing 
the solder when the flux boils rapidly. Avoid direct 
flame into the solder joint.
 5.  Heat can only be applied to the cup of the valve body 
for a minimal time before damage occurs (even with 
the use of wet rags).
Prior to connecting to the fan coil, 
all external piping must be purged 
of debris.
When  connecting  piping  or  valve 
kits to fan coil units, do not bend or 
reposition the coil header tubing for 
alignment purposes. This could cause 
a tubing fracture resulting in a water 
leak when water pressure is applied 
to the system.