Johnson Controls Unitary Products
Air Handling Unit and Steam Coil Accessory Heating Capacity
NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH
ND360 / 1NF0454
UNIT
MODEL
STEAM COIL
MODEL
CAPACITY (MBH) @ 2 PSIG
1
1
These capacities do not include any blower motor heat.
CFM
DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)
10
30
50
70
ND360
1NF0454
8,000
535
483
432
380
10,000
592
535
478
422
12,000
642
580
518
456
14,000
687
621
555
489
Steam Coil Capacity Correction Factors For High Steam Pressure
STEAM PRESSURE (PSIG)
5
10
15
20
25
CAPACITY CORRECTION FACTOR
1.05
1.12
1.19
1.25