INSTALLATION
FORM 115.20-NOM4 (105)
RECEIVING
Material in this shipment has been inspected at the 
factory and released to the transportation agency in 
good condition. When received, a visual inspection of 
all cartons should be made immediately. Any evidence 
of rough handling or apparent damage should be noted 
on the delivery receipt and the material inspected in 
the presence of the carrier’s representative.
STORAGE
If the equipment is not to be immediately installed, 
store it in a dry location with the motor protected 
against moisture, dust, corrosion and physical dam-
age.
DESCRIPTION
The YMB Series 2-pipe fan coil comes with a 4-row 
cooling / heating coil and a 120V multi-speed mo-
tor.
The YMBE Series 240V, 2-pipe fan coil comes with a 
4 row-cooling coil, 240V multi-speed motor, 240/24 
transformer, and up to 25kW of factory installed elec-
tric heat.  Models with more than 10kW also include a 
circuit breaker for branch circuit protection.  Control 
voltage is 24V.
The YMBE Series fan coil comes with a 4-row cool-
ing coil, 277V multi-speed motor, and up to 10kW of 
factory installed heat.  A unit mounted disconnect is 
standard.
The YMB-HW Series 4-pipe fan coil includes a 4 row 
cooling coil, a 2, 3, or 4 row heating coil installed in 
the reheat position, and a 120V multi-speed motor.  
If damage is found, a claim should be 
filed against the carrier immediately.
HORIZONTAL APPLICATION
These fan coil units are factory assembled for horizon-
tal left side down application without any modification 
required.  To convert to horizontal right side down, 
remove horizontal drain pan and A-coil assembly, flip 
horizontal drain pan over to right side and reinstall 
horizontal drain pan and A-coil into cabinet.  Secure 
forward  edge  of  horizontal  drain  pan  with  angle 
bracket.  The unit should be leveled in such a way 
that there is slope toward the condensate drain nipple 
to assure positive drainage.
WIRING
All wiring must comply with the local and national 
code requirements.  Units are provided with wiring 
diagrams and nameplate data to provide information 
required for necessary field wiring.  All wiring must 
comply with local and national code requirements.
YMBE SERIES
Fan  coil  units  with  10kW  or  less  electric  heat  are 
provided with a terminal block for connection of one 
electrical service.  Units with 15 kW and 20kW are 
provided with dual circuit breakers for the connection 
of two electrical services and units with 25kW are pro-
vided with three circuit breakers for the connection of 
three separate electrical services (see Figure 2 & 3).
These units may be provided with a class 2 transformer 
for 24-volt control circuits.  Should any add-on equip-
ment also have a class 2 transformer furnished, care 
must be taken to prevent interconnecting outputs of 
the two transformers by using a thermostat with iso-
lating contacts.
Any devices such as fan switches or 
thermostats that have been furnished 
by  the  factory  for  field  installation 
must  be  wired  in  strict  accordance 
with the wiring diagram that is sup-
plied with the unit. Failure to do so 
could result in damage or injury.