York DM 078 User Manual

Page of 48
246645-YTG-C-0708
36
Johnson Controls Unitary Products
 
TABLE 37:  6 POINT LOAD WEIGHT
Model
Locations (lbs.)
A
B
C
D
E
F
DM078
156
140
127
185
205
228
DM090
135
110
91
142
172
211
DM102
137
112
93
145
145
214
DM120
168
151
136
198
219
244
DM150
180
161
145
212
235
262
TABLE 38:  UNIT WEIGHT
Model
Shipping Weight (lbs.)
Operating Weight (lbs.)
DM078
1046
1041
DM090
865
860
DM102
880
875
DM120
1121
1116
DM150
1200
1195
FIGURE 5 -
UNIT DIMENSIONS
See Detail
A
For Baserail
Dimensions
See Detail B
89
27
59
4-1/4
6-3/16
17-3/16
24-3/16
30-3/16
Convenience
Power
 Outlet
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
30-11/32
Control
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
LEFT
FRONT
For Drain
Dimensions
See Detail C
11-1/2
X
TABLE 39: UNIT HEIGHT
Unit Model Number
X
DM078
50 3/4
DM090
42
DM102
42
DM120
50 3/4
DM150
50 3/4
5 - 1 / 4
B a s e
P a n
1 7 - 1 3 / 1 6
V i e w   o f   W a l l   A c r o s s   f r o m   C o i l
G a s   P i p e   I n l e t
DETAIL A
TABLE 40:  UNIT CLEARANCES
Top
*
*
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
72”
Right
12”
Front
36”
Left
36”
Rear
To remove the slide-out drain pan, a rear clearance of 
60” is required. If space is unavailable, the drain pan 
can be removed through the front by separating the 
corner wall.
36”
Bottom
Units may be installed on combustible floors made from 
wood or class A, B or C roof covering materials.
0”