economizer is 2% low leakage type. The economizer has 
spring return, fully modulating damper actuators and is 
capable of introducing up to 100% outdoor air. As the out-
door air intake dampers open, the return air dampers 
close. The changeover from mechanical refrigeration to 
economizer operation is regulated by the standard single 
enthalpy input. There is an optional input dual dry bulb 
available. To meet regulated air standards, the economizer 
control accepts an optional CO
2
 
input for
 
demand ventila-
tion. With single enthalpy input, the economizer control 
monitors outdoor air. The dual enthalpy kit provides a sec-
ond input used to monitor the return air. With a dual input 
kit installed, the economizer control compares the values 
of the two enthalpy or temperature inputs and positions the 
dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood
for field installations without an ERV.
Dual Enthalpy Control, Accessory - This kit contains 
the required components to convert a single enthalpy 
economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity 
barometric relief dampers for use with horizontal flow, or 
field installed slab economizers.
Power Exhaust - This accessory installs in the unit with 
a down flow economizer. Power exhaust plugs into the 
connector in the unit bulkhead. You must purchase 
1EH0408 barometric relief when applying to a hori-
zontal flow application.
Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper 
includes a slide-in damper assembly with an outdoor air 
hood and filters. Customers have a choice of dampers 
with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper 
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the 
indoor fan motor is energized. The damper has a range 
of 0% to 100% outdoor air entry. Factory installed option 
or field installed accessory.
Smoke Detectors - The smoke detectors stop operation 
of the unit by interrupting power to the control board if 
smoke is detected within the air compartment.
CO
2
 Sensor
 
- Senses CO
2
 levels and automatically 
overrides the economizer when levels rise above the 
preset limits.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high 
pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which 
installs over the outside condenser coil and prevents 
damage to the coil fins from hail strikes. Field installed 
accessory only.
Flue Exhaust Extension Kit - In locations with wind or 
weather conditions which may interfere with proper 
exhausting of furnace combustion products, this kit can 
be installed to prevent the flue exhaust from entering 
nearby fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas 
heat units to perform in low ambient temperatures, a gas 
section heating kit is available. This kit provides electric 
heat in the gas heat controls section to ensure the gas 
valve and controls will continue to function properly at 
extremely low temperatures.
Gas Heat High Altitude Kit - This kit converts a gas heat 
unit to operate at high altitudes, 2,000 to 6,000 feet. Con-
version kits are available for natural gas and propane.
Gas Heat Propane Conversion Kit - This kit converts a 
gas-fired heater from natural gas to propane. It contains the 
main burner orifices and gas valve replacement springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas 
cock required for gas supply connection with external 
shut off.
Electric Heaters - The electric heaters range from 9 kW 
to 54kW and are available in all the voltage options of the 
base units. All heaters are dual staged. Cooling units 
include an adapter panel for easy installation of the elec-
tric heaters. Necessary hardware and connectors are 
included with the heaters. All heaters are intended for 
single point power supply.
Low Limit / Compressor Lockout Kit
1.
Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during 
cold outdoor conditions where there is a risk of 
returning liquid refrigerant back to the compressors. 
2.
Low Limit Control (LLC): To prevent the supply air 
from dropping below a specified setpoint by utilizing 
the units first stage heating means when there is a 
demand for cooling during cold outside conditions. 
Metal Frame Filter Kit - Metal frame with polyester filter 
medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and 
are shipped disassembled The roof curbs are available 
in 8” and 14” heights. For applications with security con-
cerns, burglar bars are available for the duct openings of 
the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High) - 
Roof curbs for transitioning from Sunline™ units to Preda-
tor
®
 units. Fits 7.5 to 12.5 Sunline™
 
roof curbs only.
Burglar Bars - Mount in the supply and return openings 
to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24- 
volt electronic and electro-mechanical thermostats. All 
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only ther-
mostats, depending upon unit configuration.