York YPAL 060 User Manual

Page of 168
141
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
7
TABLE 7-1 – DEFINITIONS
Continued on next page
SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
MENU ITEM
DEFINITION
ACCUMULATED UNOCCUPIED OVERRIDE TIME
THIS PARAMETER GIVES THE ACCUMULATED TIME THE UNIT 
HAS PLACED IN UNOCCUPIED OVERRIDE MODE.
ACTIVE ALARM
THIS IDENTIFIES THE NUMBER OF ACTIVE ALARMS PRESENT
ADDRESS
THIS PARAMETER IS USED TO SET THE COMMUNICATION 
ADDRESS FOR THE UNIT WHEN CONNECTED TO A NETWORK
APS DATA
THIS PARAMETER GIVES THE STATUS OF THE SUPPLY FAN AIR 
PROVING SWITCH.  0 = SWITCH OPEN, 1 = SWITCH CLOSED
BUILDING PRESSURE SETPOINT
THIS PARAMETER ESTABLISHES THE BUILDING PRESSURE 
SETPOINT FOR THE CONTROL OF BUILDING EXHAUST 
OPERATION
BUILDING STATIC PRESSURE  
THIS PARAMETER GIVES THE CURRENT VALUE OF THE 
BUILDING STATIC PRESSURE INPUT
BUILDING STATIC PRESSURE SENSOR 
INSTALLED
THIS PARAMETER MUST BE TURNED ON TO ENABLE THE USE 
OF BUILDING PRESSURE IN THE OPERATION OF THE EXHAUST 
FUNCTION
COMFORT VENTILATION FOR COOLING 
ENABLED
THIS PARAMETER MUST BE TURNED ON TO ENABLED 
COMFORT VENTILATION  DURING COOLING MODE OPERATION 
ON A CONSTANT VOLUME UNIT
COMFORT VENTILATION FOR HEATING 
ENABLED
THIS PARAMETER MUST BE TURNED ON TO ENABLE COMFORT 
VENTILATION DURING HEATING MODE OPERATION ON A 
CONSTANT VOLUME UNIT
COMFORT VENTILATION LOWER SETPOINT
THIS PARAMETER IS THE LOWER SETPOINT USED BY THE UNIT 
CONTROLLER TO DETERMINE WHEN TO SWITCH THE UNIT IN 
COMFORT VENTILATION MODE
COMFORT VENTILATION UPPER SETPOINT
THIS PARAMETER IS THE UPPER SETPOINT USED BY THE UNIT 
CONTROLLER TO DETERMINE WHEN TO SWITCH THE UNIT IN 
COMFORT VENTILATION MODE
COMP 1 ASCD ACTIVE
THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE 
TIMER.  ON MEANS THE COMPRESSOR 1 IS IN THIS MODE
COMP 1 ASCD TIMER
THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR 
COMPRESSOR 1 IN SECONDS.
COMP 1 MIN RUN TIME
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR 
COMPRESSOR 1 IN SECONDS.
COMP 1 OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE 
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 1
COMP 1 OVERLOAD SWITCH
THIS IS THE STATUS OF THE BINARY INPUT FROM THE 
COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 1 TO 
THE UNIT CONTROLLER.  ON - OKAY, OFF - FAULTED.
COMP 2 ASCD ACTIVE
THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE 
TIMER.  ON MEANS THE COMPRESSOR 2 IS IN THIS MODE
COMP 2 ASCD TIMER
THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR 
COMPRESSOR 2 IN SECONDS.
COMP 2 MIN RUN TIME
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR 
COMPRESSOR 2 IN SECONDS.