The Discharge Transducer has a range of 0 to 650 
PSIG, with a linear output of 0 to 5 DC volts.  Table 
8-5 illustrates the DC volt output from the transducer 
for a given discharge pressure.
Suction Pressure Transducer
The optional suction pressure transducer is located in 
the common suction line of the tandem compressors for 
each refrigerant circuit.  The purpose of the transducer 
is to sense and convert the suction pressure to a DC 
voltage.  The DC voltage is then sent to the Unit 
Controller where it is displayed by the User Interface.  
When this option is installed the Unit Controller will 
also calculate and display the Evaporator Superheat 
value for the system.
The Suction Transducer has a range of 0 to 400 PSIG, 
with a linear output of 0 to 5 volts DC.  Table 8-5 
illustrates the DC volt output from the transducer for a 
given suction pressure.
Humidity Sensors
The humidity sensor outputs a 0 to 5 volts DC in response 
to the relative humidity sensed.  An outdoor air humidity 
sensor is used whenever the economizer is confi gured 
for single or dual enthalpy.  A return air humidity sensor 
is used whenever the economizer is confi gured for dual 
enthalpy.  A humidity sensor is also used to monitor 
the humidity in the space between the slab and raised 
fl oor system used for FlexSys applications.  Table 8-6 
gives the relationship between the voltage output of the 
humidity sensor and the % relative humidity.
SUCTION TRANSDUCER
DISCHARGE TRANSDUCER
PRESSURE 
PSIG
VOLTAGE 
VDC
PRESSURE 
PSIG
VOLTAGE 
VDC
0
0.5
0
0.5
25
0.75
32.5
0.7
50
1
65
0.9
75
1.25
97.5
1.1
100
1.5
130
1.3
125
1.75
162.5
1.5
150
2
195
1.7
175
2.25
227.5
1.9
200
2.5
260
2.1
225
2.75
292.5
2.3
250
3
325
2.5
275
3.25
357.5
2.7
300
3.5
390
2.9
325
3.75
422.5
3.1
350
4
455
3.3
375
4.25
487.5
3.5
400
4.5
520
3.7
552.5
3.9
585
4.1
617.5
4.3
650
4.5
TABLE 8-5 – PRESSURE TRANSDUCERS
% RELATIVE 
HUMIDITY
% RELATIVE 
HUMIDITY
5
0.25
55
2.75
10
0.50
60
3.00
15
0.75
65
3.25
20
1.00
70
3.50
25
1.25
75
3.75
30
1.50
80
4.00
35
1.75
85
4.25
40
2.00
90
4.50
45
2.25
95
4.75
50
2.50
100
5.00
TABLE 8-6 – HUMIDITY SENSOR OUTPUTS