SECTION 2 – INSTALLATION
APPROVALS
Designed certifi ed by CSA, ETL, CETL as follows:
  1. For use as a forced air furnace with cooling unit 
(gas heat models).
  2. For outdoor installation only.
  3. For installation on combustible ma te ri al  and  may 
be installed directly on combustible fl oor ing  or 
Class A, Class B or Class C roof covering ma te -
ri als.
  4. For use with natural gas or LP.
  5. When used with LP propane gas one of the follow-
ing conversion kits must be installed before the gas 
heat section is fi red:
     
375,000 BTU Input - 385-01866-001
     
750,000 BTU Input - 385-01866-002
     
1,125,000 BTU Input - 385-01866-003
Not suitable for use with conventional venting 
systems.
LIMITATIONS
The installation of this unit must conform to local 
build ing codes, or in the absence of local codes, with 
ANSI 223.1 Natural Fuel Gas Code and /or CAN/CGA 
B149 in stal la tion  codes.
In U.S.A.:
  1. National Electrical Code ANSI/NFPA No. 70 - Lat-
est Edition.
  2. National Fuel Gas Code Z223.1 - Latest Edition.
  3. Gas-Fired Central Furnace Standard ANSI Z21.47 
- Latest Edition.
  4. Local gas utility requirements.
TABLE 2-1 – VOLTAGE LIMITATIONS
UNIT POWER
SUPPLY
VOLTAGE VARIATIONS
MIN. VOLTS
MAX. VOLTS
575-3-60
518
632
480-3-60
415
506
230-3-60
207
253
200-3-60
187
228
Refer to Table 2-15 for airfl ow and entering air/ambient 
conditions limitations, and Table 2-1 for voltage 
limitations.
If the VAV boxes in the conditioned 
space have hydronic heating coils 
installed, it is the responsibility of the 
installing contractor to take appropri-
ate measures to protect the hydronic 
coils against low unit supply air tem-
peratures that could result in the freeze 
up and rupture of the coils.
UNIT INSPECTION
Immediately upon receiving the unit, it should be 
in spect ed for possible damage, which may have 
oc curred during transit. If damage is evident, it should 
be noted in the car ri er’s freight bill. A writ ten re quest 
for in spec tion by the carrier’s agent should be made at 
once. See  “In struc tion”  man u al,  Form  50.15-NM  for 
more  in for ma tion  and  de tails.
To ensure warranty cov er age, this 
equip ment must be commissioned and 
serviced by an authorized JOHNSON 
CONTROLS ser vice mechanic or a 
qual i fi ed service person ex pe ri enced 
in pack aged roof top in stal la tion. 
In stal la tion must comply with all ap-
 pli ca ble  codes,  par tic u lar ly  in  regard 
to elec tri cal  wir ing  and  other  safety 
el e ments such as relief valves, HP 
cut-out settings, de sign work ing pres-
 sures,  and  ven ti la tion  re quire ments 
con sis tent with the amount and type 
of  re frig er ant  charge.
Lethal voltages exist within the con trol 
panels. Before servicing, open and tag 
all dis con nect  switches.
LOCATIONS AND CLEARANCES
GENERAL
The eco
2
 air conditioning units are designed for outdoor 
installation. When selecting a site for installation, be 
guided by the following conditions:
 •  Unit must be installed on a level surface.
 •  For the outdoor location of the unit, select a place 
having a minimum sun exposure and an adequate 
supply of fresh air for the condenser.