York YPAL 060 User Manual

Page of 168
73
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
5
• 
If the outdoor air temperature is less then the 
economizer supply air temperature set point, 
compressors will not operate regardless of the 
“OUTDOOR AIR TEMP COOLING LOCK-
OUT” 
set point.
 
LOW AMBIENT OPERATION 
 
A condenser fan VFD can be installed on condenser 
fan # l. When this is installed compressor system 1 
(compressors 1A and 1B) can operate down to an 
outdoor temperature of 0.0º F. The VFD is located in 
an enclosure on the right hand side of the condenser 
section, to the right of the system 2 compressors. 
 
To enable low ambient operation when a condenser 
fan VFD is installed, the following parameter must be 
programmed:
 
“LOWAMBIENT KITINSTALLED” - is enabled 
using Parameter 84 under the PROGRAM key 
of the Simplicity Elite control board or under the 
EQUIPMENT INSTALLATION tab in the Simplicity 
PC software package.  
Operation and Pressure Control Range
The VFD controls the speed of the fan based on a 
discharge pressure setpoint and a differential range.  
When discharge pressure reaches approximately 270 
PSIG, the VFD will start the fan if the Unit Controller 
is calling for compressor / condenser fan operation.  The 
binary outputs from the Unit Controller are as shown 
in Table 5-1.  
TABLE 5-1 – BINARY OUTPUTS
CONDENSER
FAN
CONNECTOR
TERMINAL
#
WIRE
CONTACTOR
1A
P13
1
423
6M
As soon as the contactor is energized, the VFD will be 
activated and will begin to control.  As the pressure rises 
over the next 80 PSIG (270 – 350 PSIG); the fan speed 
will increase to full speed at approximately 350 PSIG.
The VFD control input signal originates from the 
discharge pressure transducer for the compressor system 
it is controlling.  The transducer signal feeds the VFD.  
The VFD controls the fan speed based on discharge 
pressure.
Confi guration (Jumpers and Potentiometers)
The inverter is confi gured at the factory.  The  jumpers 
must be in the positions shown in Table 5-2.
TABLE 5-2 – VFD JUMPERS
J2
REMOVE
-
J3
REMOVE
J4
REMOVE
J5
MIDDLE
J6
MIDDLE
J7
IN
J8
IN
J9
IN FOR 60 HZ
REMOVE FOR 50 HZ
Potentiometer settings are also preset at the factory.  
The potentiometers should be in the positions shown in 
Table 5-3.  The potentiometers do not have numerical 
settings and are set according to the positions indicated.  
DO NOT change potentiometer settings unless they do 
not match the positioning of the potentiometers shown 
in Figure 5-1.  Modifying these settings may cause 
damage to the unit, control problems, and/or poor 
operating effi ciency.
TABLE 5-3 – POTENTIOMETER SETTINGS
P1
P2
350 PSIG
80 PSIG
6 O’CLOCK
6 O’CLOCK
P1
P2
P1
P2
FIG. 5-1 –  CONDENSER FAN VFD POTENTIOMETER 
SETTINGS
LD113008