Single Enthalpy
The following parameters must be programmed to allow 
economizer operation:
“ E C O N O M I Z E R   O U T S I D E  A I R   E N T H A L P Y 
SETPOINT”
 – must be programmed using Parameter 
37 under the PROGRAM key on the Simplicity control 
board or under the ECONOMIZER/EXHAUST tab in 
the Simplicity PC software package.
“OUTSIDE AIR HUMIDITY SENSOR INSTALLED” 
– must be enabled using Parameter 36 under the 
PROGRAM key on the Simplicity control board or 
under the EQUIPMENT INSTALLATION tab in the 
Simplicity PC software package.
The economizer will become active and use outdoor air 
for cooling when:
  The outside air enthalpy is less then or equal to 
the “ECONOMIZER OUTSIDE AIR ENTHALPY 
SETPOINT”.
  The Simplicity Control has a demand for cooling 
operation.
  If the outdoor air enthalpy was above the 
“ECONOMIZER OUTSIDE AIR ENTHALPY  
SETPOINT”
 when the cooling cycle was initiated 
the Simplicity Control will activate economizer 
operation when the outdoor air enthalpy is 1.0 
BTU/LB below the “ECONOMIZER OUTSIDE 
AIR ENTHALPY SETPOINT”
.
The economizer will become inactive and eliminate the 
use of outdoor air for cooling when:
  The outside air enthalpy is 1.0 BTU/LB greater 
than the “ECONOMIZER OUTSIDE AIR 
ENTHALPY SETPOINT”
.
  The Simplicity Control does not have an Occu-
pied or Unoccupied cooling demand.
Dual Enthalpy
The following parameter must be programmed to allow 
economizer operation:
“RETURN AIR HUMIDITY SENSOR INSTALLED” 
– must be enabled using Parameter 38 under the 
PROGRAM key on the Simplicity control board or 
under the EQUIPMENT INSTALLATION tab in the 
Simplicity PC software package.
“DIFFERENTIAL ENTHALPY MODE ENABLED” must 
be turned ON under the ECONOMIZER/EXHAUST tab 
in the Simplicity PC software package.
The economizer will become active and use outdoor air 
for cooling when:
  The outside air enthalpy is 1.0 BTU/LB less then 
the return air enthalpy.
  The Simplicity Control has a demand for cooling 
operation.
The economizer will become inactive and eliminate the 
use of outdoor air for cooling when:
  The outside air enthalpy is equal to or greater 
than the return air enthalpy.
  The Simplicity Control does not have an Occu-
pied or Unoccupied cooling demand.
BAS ECONOMIZER OPERATION 
 
This feature allows the outdoor/return air damper to be 
controlled by an external 2 to 10 VDC input. 
The following parameters must be programmed to allow 
BAS ECONOMIZER OPERATION: 
“ECONOMIZER INSTALLED” - must be disabled using 
Parameter 32 under the PROGRAM key on the Simplicity 
Control board or under the ECONOMIZER/EXHAUST 
tab in the Simplicity PC software package.