York HFC-410A User Manual

Page of 44
FORM 100.50-EG5 (108)
23
JOHNSON CONTROLS
Supply Fan Data
TABLE 12 – 28" x 28" FORWARD-CURVED FAN
Total Static Pressure (inches of water column)
CFM 
STD. AIR
1.0
2.0
3.0
4.0
5.0
6.0
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
12000
12.3
639
16.8
730
21.5
808
26.4
879
14000
14.3
642
19.2
738
24.3
818
29.7
890
16000
10.8
528
16.2
642
21.8
742
27.3
826
33.2
900
18000
12.7
537
18
643
24.4
742
30.6
829
36.8
906
20000
10.4
447
15
550
20.3
648
26.8
742
33.9
830
40.8
908
22000
12.9
471
17.6
566
23.3
657
29.4
745
36.9
830
24000
15.7
496
20.8
586
26.8
700
33
752
40
832
26000
19.1
522
24.5
607
30.5
686
37.3
762
 
 
 
 
 
 
 
 
 
 
 
TABLE 13 – 28" AIRFOIL FAN
Total Static Pressure (inches of water column)
CFM 
STD. AIR
1.0
2.0
3.0
4.0
5.0
6.0
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
12000
12.6
1133
15.9
1241
19.5
1343
14000
5.2
806
8.1
947
11.4
1068
14.8
1177
18.4
1278
22.1
1374
16000
6.8
877
10
1011
13.5
1125
17.3
1228
21.2
1324
25.2
1415
18000
8.7
951
12.3
1077
16
1186
20.1
1285
24.3
1376
28.7
1462
20000
10.9
1027
15
1146
19
1251
23.3
1345
27.9
1433
32.6
1515
22000
13.6
1105
18.1
1218
22.4
1318
26.9
1409
31.8
1493
36.8
1572
24000
16.6
1184
21.7
1291
26.5
1387
31.2
1474
36.2
1556
26000
20.2
1265
25.7
1366
31
1457
36.1
1542