York HFC-410A User Manual

Page of 44
JOHNSON CONTROLS
26
FORM 100.50-EG5 (108)
Electrical Data
ELECTRICAL SERVICE SIZING
In order to use the electrical service required for the cool-
ing-only Eco
2
 rooftop, use the appropriate calculations 
listed below from U.L. 1995. Based on the confi guration 
of the rooftop, the calculations will yield different MCA 
(minimum circuit ampacity), and MOP (maximum over-
current protection).
Using the following load defi nitions and calculations, 
determine the correct electrical sizing for your unit. All 
concurrent load conditions must be considered in the 
calculations, and you must use the highest value for any 
combination of loads.
Load Defi nitions:
 •  LOAD1 is the current of the largest motor – com-
pressor or fan motor.
 •  LOAD2 is the sum of the remaining motor currents 
that may run concurrently with LOAD1.
 •  LOAD3 is the current of the electric heaters – zero 
for cooling-only units.
 •  LOAD4 is the sum of any remaining currents greater 
than or equal to 1.0 amp.
Use the following calculations to determine MCA and 
MOP for units supplied with a single-point power con-
nection:
 
MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
  MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
If the MOP does not equal a standard current rating 
of an overcurrent protective device, then the marked 
maximum rating is to be the next lower standard rating. 
However, if the device selected for MOP is less than the 
MCA, then select the lowest standard maximum fuse 
size greater than or equal to the MCA.
TABLE 16 – COMPRESSOR ELECTRICAL DATA
Model
Compressor
Model
Nominal Voltage
208-230/3/60
460/3/60
575/3/60
RLA*
LRA
RLA*
LRA
RLA*
LRA
050
1A
ZP120
33.3
239
17.9
125
12.8
80
1B
ZP137
48.0
245
18.6
125
14.7
100
2A
ZP121
33.3
239
17.9
125
12.8
80
2B
ZP137
48.0
245
18.6
125
14.7
100
051
1A
ZP137
48.0
245
18.6
125
14.7
100
1B
ZP137
48.0
245
18.6
125
14.7
100
2A
ZP137
48.0
245
18.6
125
14.7
100
2B
ZP137
48.0
245
18.6
125
14.7
100
060
1A
ZP137
48.0
245
18.6
125
14.7
100
1B
ZP182
55.7
340
26.9
172
23.7
132
2A
ZP137
48.0
245
18.6
125
14.7
100
2B
ZP182
55.7
340
26.9
172
23.7
132
061
1A
ZP154
51.3
300
22.4
150
19.8
109
1B
ZP182
55.7
340
25.0
172
23.7
132
2A
ZP137
48.0
245
18.6
125
14.7
100
2B
ZP182
55.7
340
25.0
172
23.7
132
TABLE 17 – POWER SUPPLY VOLTAGE LIMITS
Power Supply
Minimum Voltage
Maximum Voltage
208V/3Ph/60Hz
187
228
230V/3Ph/60Hz
207
253
460V/3Ph/60Hz
414
506
575V/3Ph/60Hz
518
632