York HFC-410A User Manual

Page of 44
JOHNSON CONTROLS
4
FORM 100.50-EG5 (108)
Features and Benefi ts
AIRFLOW CONFIGURATIONS
Variable-Air-Volume – Eco
2
 units are available for 
single-zone variable-air-volume (VAV) applications. 
Supply fans are controlled to the supply duct static 
pressure setpoint, which can be reset via a BAS, or 
through an analog voltage input on the unit controller 
for optimized duct static pressure control. The static 
pressure transducer is provided in the rooftop unit, and 
5/16” or 1/4” plastic tubing and static pressure sensor 
must be supplied by others and installed approximately 
3/4 down the longest duct run.
Constant Volume – Eco
2
 units are available for single-
zone constant volume applications. Control can be used 
with a zone sensor, thermostat, or building automation 
system.
COOLING AND HEATING CONFIGURATIONS
Cooling Only – For applications where no heat is 
required, or heating is provided elsewhere within the 
building HVAC system, cooling only units include an 
empty discharge plenum. Supply duct connections are 
confi gurable for bottom, left or right discharge. The 
supply air temperature sensor is included and factory-
installed.
Staged Gas Heat – For applications requiring gas heat 
for morning warm-up, or other heating needs, a staged 
natural gas furnace is available. The furnace is located 
in the discharge plenum, downstream of the supply fan. 
The supply air temperature sensor is located across the 
face of the supply duct opening in the unit. Furnaces 
are designed in 375 mbh modules with one stage each. 
Three are available on the YPAL050-061 with bottom 
discharge and two are available on the YPAL050-061 
with left-side discharge. Ignition and safety controls are 
included and factory-wired. 
POWER OPTIONS
Single-point supply with terminal block – This 
confi guration is standard, and includes three terminals 
for the incoming 3-phase power and is the standard 
confi guration for the Eco
2
 product. It includes the en-
closure, terminal-block, and interconnecting wiring to 
the compressors, heater and furnace controls, all fans, 
etc. In this confi guration, code requires that a means of 
disconnect (not provided) must be installed at the site 
within line-of-sight of the equipment.
Single-point supply with non-fused disconnect switch 
– This option is the same the single-point with terminal 
block option except it includes a unit-mounted through-
the-door manual non-fused disconnect switch with an 
external, lockable handle (in compliance with Article 
440-14 of N.E.C.). This option provides a means to 
isolate the unit power voltage for servicing. Others must 
supply separate external fusing which must comply with 
the National Electric Code and/or local codes.
Dual-point supply with terminal block – This option in-
cludes enclosure, terminal blocks circuited to the supply 
and exhaust fans and control transformer and a second 
set of terminal blocks with interconnecting wiring to the 
compressors, heat (if applicable) and condenser.
Convenience Outlet – This options includes a powered 
115V GFCI convenience outlet that can be used for 
powering tools or lights for servicing. A protective cover 
plate is included while not in use. The outlet is located 
on the bottom left hand corner of the power panel.
CONTROL FEATURES AND OPTIONS
Simplicity Elite Unit Controller – All Eco
2
 units are 
equipped with a factory-installed, programmed and 
commissioned unit controller with all I/O capabilities and 
control sequences. The controls include all on-board 
diagnostic, safety and control features to operate the 
rooftop unit. Two RS485 communication ports are in-
cluded as standard with one alarm output, a shutdown 
contact, smoke ventilation contact, analog inputs for 
supply air temperature and duct static pressure reset, 
along with a variety of other capabilities.
Standard Ambient – YPAL050-061 models operate 
down to 40°F as standard. 
Low Ambient – This option includes low ambient control 
of the fi rst refrigerant circuit down to 0°F through the 
use of suction and discharge pressure transducer on 
circuit one, and condenser fan speed using a variable-
frequency drive on the fi rst condenser fan of circuit one. 
Mechanical cooling with circuit two is locked out below 
45°F (adjustable).
Flexsys bypass control option is not available with elite 
controller.  
SENSOR AND THERMOSTAT AND SENSOR
OPTIONS
Wall-Mount Zone Sensor – A thermistor zone sen-
sor for wall mounting. This zone sensor is for sensing 
temperature only, and does not include any setpoint 
adjustment features.
7-Wire Thermostat – This option is for a ship-loose 
thermostat to interface with the Eco
2
 unit. All models, 
YPAL050-061, include an interface for a 7-wire ther-
mostat as standard.