York DNP036 User Manual

Page of 36
036-21366-007-A-1205
Unitary Products Group
19
FIGURE 4 -  POWER WIRING FIELD DIAGRAM
 
G R O U N D
L U G
R E F E R   T O   E L E C T R I C A L
D A T A   T A B L E S   T O   S I Z E
T H E   D I S C O N N E C T
F I E L D - S U P P L I E D
D I S C O N N E C T
C O N T A C T O R
F I E L D - S U P P L I E D
D I S C O N N E C T
C O N T A C T O R
G R O U N D
L U G
R E F E R   T O   E L E C T R I C A L
D A T A   T A B L E S   T O   S I Z E
T H E   D I S C O N N E C T
S I N G L E
P H A S E
P O W E R
S U P P L Y
T H R E E
P H A S E
P O W E R
S U P P L Y
TABLE 14: ELECTRICAL DATA
MODEL
DNP
POWER SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
024
208/230-1-60
187
253
8.0
53.5
1.1
2.6
16.5
20
20
0.96
40
030
208/230-1-60
187
253
13.6
67
1.1
6.8
24.9
35
35
0.96
40
030
208/230-3-60
187
253
8.6
55
1.1
6.8
18.7
25
25
0.96
75
030
460-3-60
432
504
5.7
39
0.6
6.8
13.4
20
20
0.96
75
036
208/230-1-60
187
253
17.2
88
1.1
6.8
29.4
45
45
0.96
40
036
208/230-3-60
187
253
11.4
77
1.1
6.8
22.2
30
30
0.96
75
036
460-3-60
432
504
5.7
39
0.6
6.8
14.8
20
20
0.96
75
036
575-3-60
540
630
4.7
31
0.6
6.8
13.3
20
20
0.96
75
042
208/230-1-60
187
253
20
104
1.3
9.1
35.4
50
50
0.96
40
042
208/230-3-60
187
253
13.9
88
1.3
9.1
27.8
40
40
0.96
75
042
460-3-60
432
504
6.4
44
0.7
9.1
18.5
25
25
0.96
75
042
575-3-60
540
630
5.4
34
0.6
9.1
16.8
25
25
0.96
75
048
208/230-1-60
187
253
23.4
126
1.9
9.1
39.5
60
60
0.96
40
048
208/230-3-60
187
253
13
93
1.9
9.1
26.5
35
35
0.96
75
048
460-3-60
432
504
6.4
46.5
1.0
9.1
18.4
25
25
0.96
75
048
575-3-60
540
630
5.1
37.2
0.8
9.1
17.3
25
25
0.96
75
060
208/230-1-60
187
253
25
150
2.8
9.1
43.2
60
60
0.96
40
060
208/230-3-60
187
253
17.3
123
2.8
9.1
33.5
45
45
0.96
75
060
460-3-60
432
504
8.4
70
2.8
9.1
22.6
30
30
0.96
75
060
575-3-60
540
630
7.0
53
2.8
9.1
21.2
30
30
0.96
75
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Dual element, time delay type.