York DM 240 User Manual

Page of 40
262259-YTG-B-0107
Unitary Products Group
39
temperature. Unit shall be provided with fan time delay to 
prevent cold air delivery before heat exchanger warms up 
(Gas heat only). 
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring. 
STANDARD LIMITED WARRANTIES
Compressor 5 Years
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by 
either/or): 
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER
 - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss. 
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and 
return air dampers that are interlocked and positioned by 
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG. A 
unit-mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in 
the design CFM of outdoor air to meet the ventilation 
requirements of the conditioned space during normal 
operation. Whenever the indoor fan motor is energized, 
the dampers open up to one of two pre-selected posi-
tions - regardless of the outdoor air enthalpy. Dampers 
return to the fully closed position when the indoor fan 
motor is de-energized. Dampers shall fully close on 
power loss. 
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
ROOF CURB - 14" high, full perimeter curb with wood 
nailer (shipped knocked-down). 
100% BAROMETRIC RELIEF DAMPER - Contains a 
rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure 
through the unit. 
PROPANE CONVERSION KIT - Contains new orifices 
and gas valve parts to convert from natural to L.P. gas. 
One per unit required. 
HIGH ALTITUDE - NATURAL GAS - Contains orifices 
required for applications between 2000 and 6000 feet 
altitude. 
HIGH ALTITUDE - PROPANE GAS - Contains orifices 
required for applications between 2000 and 6000 feet 
altitude. Must be used with propane conversion kit. 
BURGLAR BARS - Designed to work with above roof 
curbs, depending on unit model. Fits duct openings of 
curb supply and return air openings. 
SIDE DUCT FLANGE - Supply and return air duct 
flanges for side duct applications. Do not use on units 
with power exhaust. 
HIGH SPEED DRIVE - Includes blower pulley and belt 
for higher CFM and/or static pressure requirements. 
WOOD SKID - Allows unit to be handled with 90" forks. 
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD 
(DMN/E/C300 only)
 - Contains all hood panels and the 
hardware for assembling. 
ANTI-RECYCLE TIMER - Assures 5-minute off time 
between compressor cycles.
COIL GUARD KIT - Guard for cooling coil. 
OTHER FACTORY INSTALLED OPTIONS
POWER EXHAUST OPTION - To work in conjunction 
with economizers.
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
TECHNICOAT PHENOLIC COATED CONDENSER 
AND EVAPORATOR COIL
ELECTRONIC SINGLE ENTHALPY ECONOMIZER 
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
BAS CONTROLS (Simplicity® INTELLI-Comfort™ CPC, 
JOHNSON, HONEYWELL, NOVAR)
BAS READY ECONOMIZER (BELIMO ACTUATOR 
WITHOUT A CONTROLLER)