York K4EU090 User Manual

Page of 28
036-21300-002-A-0905
Unitary Products Group
7
TABLE 4: HEATING CAPACITY - ELECTRIC HEAT ACCESSORY
UNIT MODEL
HEATER MODEL
VOLTAGE TEST
NOMINAL RATINGS
1
CAPACITY
1ST STAGE
2ND STAGE
KW
MBH
KW
MBH
KW
MBH
060
2HT045010
25
208 / 240
2
10
34.2
10
34.2
-
-
2HT045016
25
208 / 240
16
54.7
10
34.2
6
20.5
2HT045026
25
208 / 240
26
88.9
16
54.7
10
34.2
090, 120
2HS045010
25
208 / 240
10
34.2
10
34.2
-
-
46
480
3
58
600
4
2HS045016
25
208 / 240
16
54.7
10
34.2
6
20.5
46
58
2HS045026
25
208 / 240
26
88.9
16
54.7
10
34.2
46
58
2HS045036
25
208 / 240
36
123
16
54.7
20
68.3
46
58
180
2HS045010
25
208 / 240
10
34.2
10
34.2
-
-
46
58
2HS045016
25
208 / 240
16
54.7
10
34.2
6
20.5
46
58
2HS045026
25
208 / 240
26
88.9
16
54.7
10
34.2
46
58
2HS045036
25
208 / 240
36
123
16
54.7
20
68.3
46
58
2HS045072
25
208 / 240
72
246
36
123
36
123
46
58
1. Capacity Ratings do not include the heat generated by the air blower motor.
2. For 208 volts, multiply the MBH and KW by (208/240)² or 0.751.
For 230 volts, multiply the MBH and KW by (230/240)² or 0.918.
3. For 460 volts, multiply the MBH and KW by (460/480)² or 0.918.
4. For 575 volts, multiply the MBH and KW by (575/600)² or 0.918.