York D2HE/D2HG060 User Manual

Page of 28
036-21216-003-A-0204
Unitary Products Group
19
NOTE: DHG modes must be provided a 1” clearance 
between any combustible material and the supply 
air ductwork for a distance of 2 feet from the unit.
The products of combustion must not be allowed to accumu-
late with a confined space and recirculate.  Locate unit so that 
the vent air outlet hood is at least.
Three feet above any forced air inlet located within 10 
horizontal feet (excluding those integral to the unit).
Four feet below, 4 horizontal feet from, or 1 foot above 
any door or gravity air inlet into the building.
Four feet from electric meters, gas meters, regulators 
and relief equipment.
FIGURE 9 -  UNIT DIMENSIONS DHG UNIT
TABLE 20: CLEARANCES
FRONT
DHE UNITS
24”
DHG UNITS
32”
BACK
12” (Less Economizer)
36” (With Economizer or 
Fixed Air/Motorized 
Damper)
LEFT SIDE (Filter Access)
24” (Less Economizer)
36” (With Economizer)
RIGHT SIDE (Cond. Coil)
24”
BELOW UNIT
1
1.
Units may be installed on combustible floors made from 
wood or class A, B, or C roof covering material.
0”
ABOVE UNIT
2
2.
Units must be installed outdoors.  Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
72” (For Condenser Air 
Discharge)
R E T U R N   A I R
S U P P L Y   A I R
O U T D O O R   A I R
O U T D O O R   A I R
( E c o n o m i z e r )
All dimensions are in inches.  They are 
subject to change without notice.  Certi-
fied dimensions will be provided upon 
request.