MAINTENANCE
MOTOR
The blower motor should be cleaned annually and if it 
has oiling ports, it should be oiled with a good grade of 
SAE 20 oil. Normally a few drops of oil in each bearing 
is sufficient.
COIL
The coil must be kept clean by any of the following 
methods.
 1.   Cleaning with low-pressure compressed air.
 2.   Flushing or rinsing with water (a detergent is ad-
visable for greasy surfaces).
 3.   Prior to the water system start-up and balancing, the 
chilled/hot water systems should be flushed to clean 
out dirt and debris, which may have accumulated 
during construction. All unit service valves are to 
be closed during this process. Strainers are to be 
installed in the piping mains to prevent this material 
from entering the units during normal operation.
FILTERS
The  intervals  at  which  filters  require  replacement 
depend on local conditions.
Tele. 800-861-1001
www.York.com
P.O. Box 1592, York, Pennsylvania USA  17405-1592 
Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2004 
ALL RIGHTS RESERVED
Form 115.20-NOM2 (105) 
Supercedes 115.20-NOM2 (904) 
Because of dust and lint in the room, room-air filters 
load  up  much  more  rapidly  than  outdoor-air  filters.  
Under normal conditions, the room air filter requires 
replacement every six to eight weeks.
To ensure proper maintenance of the filters, it is best 
to follow an organized maintenance procedure.  The 
following one is recommended:
Divide the total number of units on the job into six 
equal groups.  Each week inspect, clean or replace the 
filters in each group, in rotation.  This insures a uniform 
servicing interval.  The interval may be lengthened or 
shortened as determined by experience.  If inspection 
shows only the room-air filter to be dirty, this one alone 
should be replaced.
Dirty filters reduce the air and heat-
ing capacities of the Unit Ventilator.  
When the filters are excessively dirty, 
the unit heating capacity will be so re-
duced that it is ineffective for heating 
the room.  When a room fails to heat, 
always check the filters.
CLEAN UNIT INTERIOR
Once  a  year  clean  the  fans  and  coils  of  the  unit 
thoroughly.  Remove the access panel as necessary.
Wipe the interior of the unit clean with a rag.  Wipe the 
motor and inside and outside of the fan housings.  (In 
cooling units, clean out the drain pan.)
Clean or Replace Air Filters Regu-
larly